6.1 Cooling Capacity
KV24CM-ARF21
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 7.52 7.15 6.79 6.50
SC 5.56 5.51 5.43 5.46
Input 2.10 2.28 2.38 2.46
24/17ºC DB/WB
TC 7.74 7.37 7.01 6.57
SC 5.80 5.75 5.68 5.52
Input 2.23 2.38 2.49 2.61
27/19ºC DB/WB
TC 7.88 7.52
7.30
6.79
SC 5.83 5.79 5.69 5.57
Input 2.28 2.41
2.54
2.66
32/23ºC DB/WB
TC 8.03 7.74 7.59 7.01
SC 6.83 6.73 6.68 6.52
Input 2.38 2.49 2.66 2.76
Notes:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power; kW