EasyManua.ls Logo

KRUEGER KLPS - Setting Fan Air Flow with ECM Motors; Manual Speed Control (Control Option 6); Remote Speed Control, 0-10 Vdc (0-20 mA) Input (Control Option 7); Remote Speed Control, 2-10 Vdc (4-20 mA) Input (Control Option 8)

KRUEGER KLPS
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
Fan Powered Terminal Units IOM
SETTING FAN AIR FLOW WITH ECM MOTORS
Several terminal unit models are available with ECM motors
for easy balancing. These motors supply a determined
amount of air regardless of static pressure from ductwork
layout or air distribution. The ECM motors are programmed
to provide a maximum CFM depending on model and unit
size. The motors are then set to provide the desired CFM as
a proportional amount of the maximum. The proportion can
be set by several options:
MANUAL SPEED CONTROL (CONTROL OPTION 6)
Manual speed controlled units are manually operated
with a digital readout on the ECM controller (see Figure
10). The digital readout provides a percent of maximum.
A fan adjustment knob is rotated until the desired percent
is displayed. After 20 seconds from nal adjustment, the
controller display will alternate between percent and motor
RPM’s. See Tables 14-28 for the percent required for desired
CFM.
REMOTE SPEED CONTROL, 0-10Vdc (0-20mA) INPUT
(CONTROL OPTION 7)
The board is factory set to accept a 0-10Vdc signal to control
the airow between 0% and 100% as shown in the chart
in Figure 11. This option does not allow for on/o control.
Setting the jumper to the “Opt” position as shown in the
Jumper Setting” in Figure 11 sets the control signal to
0-10Vdc signal.
REMOTE SPEED CONTROL, 2-10Vdc (4-20mA) INPUT
(CONTROL OPTION 8)
Another option is to have the board factory set to allow for
on/o control by setting the jumper on to the Pposition.
This setting uses a 2-10Vdc control signal range with a
voltage signal under 2Vdc turning the motor o. See gure
11 for graph of operating range.
Note: Both Remote Speed Control Options provide a
manual Override for eld setting the ECM motor without
being connected to a DDC controller. If a DDC controller
is connected, adjusting the manual override will lock out
the automation signal for 15 minutes.
FIGURE 10 –Manual Speed, ECM Controller
FIGURE 11 – Remote Speed, ECM Controller
“Opt” Jumper
“P” Jumper
Volts
Flow Index
0-10Vdc 2-10Vdc with On/O
10
9
8
7
6
5
4
3
2
1
0
0 10 20 30 40 50 60 70 80 90 100

Related product manuals