Form #: SIDOM.4 Page | 27 Revised: 03/19
Table 6.C SVE Basic Pressure and Airflow Data
SVE Basic Pressure and Airflow Performance
Inlet Size
Maximum
Airflow
(CFM)
Minimum
Airflow
(CFM)
Flow
Rate
(CFM)
Min
Ps
("W.G.)
Inlet
Size
Maximum
Airflow
(CFM)
Minimum
Airflow
(CFM)
Flow
Rate
(CFM)
Min Ps
("W.G.)
A
456
79
75
0.057
J
3938
682
682
0.048
155
0.242
1475
0.223
235
0.556
2300
0.543
315
1
3121
1
B
656
114
114
0.058
K
5104
884
884
0.032
225
0.226
2225
0.204
350
0.548
3550
0.52
473
1
4923
1
C
875
152
152
0.037
L
6563
1137
1137
0.013
350
0.198
2925
0.085
575
0.535
4725
0.222
786
1
6563
0.429
D
1458
253
253
0.079
M
6417
1111
1111
0.017
475
0.278
2850
0.11
675
0.561
4625
0.29
902
1.001
6417
0.559
E
2042
354
354
0.071
N
7875
1364
1364
0.013
675
0.258
3525
0.086
1000
0.567
5650
0.221
1328
1
7875
0.43
F
1969
351
341
0.072
P
10938
1894
1894
0.013
650
0.262
4875
0.086
950
0.56
7875
0.223
1270
1.001
10938
0.43
G
2188
379
379
0.07
R
14583
2526
2526
0.013
725
0.255
6500
0.085
1075
0.561
10475
0.221
1435
1
14583
0.429
H
3281
568
568
0.055
1175
0.237
1775
0.541
2414
1
NOTES:
1.) Minimum CFM value is based on a signal of 0.03 in w.g. differential
pressure of the inlet.