We thank you for choosing an LAE controller. Before proceeding to the installation, please read this instructions sheet carefully; only in this way you will obtain
maximum performances and safety.
1. INSTALLATION
1.1 The SMD90 must be secured to the panel by means of screws or rivets to be inserted into the appropriate slots. Protection is IP30, therefore please locate
the unit in a position ensuring that no liquid infiltrates and damages the board.
1.2 Probes, power supply and outputs must be connected strictly according to the indications appearing on the board; the cables can pass through the hole
on the unit side. For supply voltage and maximum switchable loads, please read the label on the enclosure.
The flat cable of the SMD34RU remote unit must be connected to the relevant connector, please make sure that the mechanical polarity is respected.
1.3 The front of the SMD34RU must be inserted into the panel and sandwiched with the backside cover, then finally firmly closed by means of the screws
provided with the enclosure.
1.4 Probe T1 measures the air temperature and is used for the thermostat function. Probe T2 measures the evaporator temperature and must be secured to it
in a place where the maximum frost growth occurs.
1.5 The unit works with an ambient temperature between -10°.. +50°C and 15%.. 80% relative humidity. To reduce the effects of electro-magnetic interference,
place the probe and signal cables as away as possible from power lines.
Caution: where delicate or valuable products have to be maintained under strict conditions, please use a different controller for limit and alarm functions.
2. OPERATING LEVELS
For 3 seconds from the power-up the display illuminates a dash (self-check phase). The following indications depend on the operating status of the controller and
from the menu level activated by the operator.
On table 1 you can see status, levels and indications relevant to them.
2.1 S
TANDBY
: OFF permanently displayed to show the standby status. Setting the parameter OFF=YES enables the [0/I] button that allows to put the SMD90
on standby. If OFF=NO the button [0/I] is inhibited.
On standby, output controls and buttons are excluded with the exception of light command (manually or door controlled).
2.2 N
ORMAL
: during the normal operation phases, the display shows the air temperature, however the following indications can come up: ERR probe T1 fault;
ALR alarm status; DEF defrost in progress.
2.3 I
NFO MENU
: pressing button enables the information selection menu. In this menu the instantaneous temperatures T1, T2 and the alarm status appear.
It’s also possible to start a defrost manually or set the setup access code. The selection of the data to be displayed can take place sequentially, by repeatedly
pressing , or quickly via buttons and to scroll through the menu. You exit from the menu by pressing button or automatically after 5 seconds of no
button activation.
2.4 S
ETUP
: you have got access to the parameter menu by selecting 47 as passcode PC. To achieve this press buttons and or . The exit from the
setup takes place by pressing button or after 30 seconds of no button activation.
3. CONTROL PARAMETERS
The adaptation of the controller to the system that it controls is achieved through the parameters in the setup. The available parameters appear on table 2
hereinafter. You proceed from one parameter to the next/previous by pressing button or . To display the related value, press button , to change it press
INSTRUCTIONS FOR INSTALLATION AND USE.
SMD90B35 (A-C)
SMD34RU
S
TANDBY
N
ORMAL
I
NFO MENU
I
NFO DATA
S
ETUP
P
ARAMETER
MENU VALUE
OFF -20 DF DF- ADR 255
air temperature
manual defrost waiting for peripheral
start sequence address
DEF AL A H --- ---
defrost on alarm sources high ….
temperature
ALR T1 -18 --- ---
new alarm shows air ….
temperature
ERR T2 -22 SPH -18
probe 1 failure shows coil maximum
temperature setpoint
PC 47 SPL -25
pass code minimum
setting setpoint
Table 1
Question and Answer IconNeed help?

Do you have a question about the LAE SMD34RU and is the answer not in the manual?

LAE SMD34RU Specifications

General IconGeneral
BrandLAE
ModelSMD34RU
CategoryController
LanguageEnglish

Summary

Installation Guide

Unit Mounting and Protection

Secure unit with screws/rivets, protect from liquid infiltration.

Cable Connections and Polarity

Connect probes and power supply per board indications; respect mechanical polarity.

Front Panel Installation

Insert the front panel into the unit and secure with screws.

Probe Placement and Function

T1 for air temperature, T2 for evaporator temperature at maximum frost growth.

Operating Environment and Interference

Operates between -10°C to +50°C; avoid placing signal cables near power lines.

Operating Levels and Modes

Standby Mode

OFF is displayed; [0/1] button enables standby if parameter OFF=YES.

Normal Operation Display

Shows air temp; indicates ERR (probe fault), ALR (alarm), DEF (defrost).

Info Menu Navigation

Access T1, T2 temps, alarm status; start manual defrost or setup access code.

Setup Menu Access

Access parameter menu using passcode PC 47 via specific buttons.

Control Parameters and Displays

Parameter Overview

Parameters adapt controller to system; navigate and change values using buttons.

Temperature Display Options

Displays T1/T2 corrected by offsets OS1/OS2; selectable Celsius/Fahrenheit via SCL.

Core Control Functions

Thermostat Operation

Compares T1 to setpoint SP and hysteresis HYS for heating/cooling control.

Probe T1 Failure Mode

Displays ERR, controls output with fixed time based on CDC parameter.

Defrost Cycle Management

Automatic start based on DFR timer; manual start via Info Menu.

Defrost Output Control

Controls compressor, fans, and defrost relay based on DTY parameter.

Defrost Termination

Terminates by DTO time or DLI temp; includes DRN phase for ice melting.

Advanced Functions and Alarms

Evaporator Fan Control Logic

Fans cycle based on FRC parameter, proportionate to compressor run time.

Door Switch Fan Control

If DS=YES, fans stop immediately upon door opening.

Fan Re-start After Defrost

Fans re-start when evaporator temperature is below FDR.

Temperature Alarm Settings

ATL/ATH define alarm differentials for low/high temperatures.

Door Alarm and Condenser Warnings

Door alarm enabled by DS=YES; condenser clean warning via ACL parameter.

Alarm Indication and Muting

Displays alarm codes (AH, AL, AD, etc.); mute buzzer with button, relay stays active.

Lighting and Serial Communication

Control lights manually or via door switch (DS, LDC=YES); RS485 for supervisory software.