Secure unit with screws/rivets, protect from liquid infiltration.
Connect probes and power supply per board indications; respect mechanical polarity.
Insert the front panel into the unit and secure with screws.
T1 for air temperature, T2 for evaporator temperature at maximum frost growth.
Operates between -10°C to +50°C; avoid placing signal cables near power lines.
OFF is displayed; [0/1] button enables standby if parameter OFF=YES.
Shows air temp; indicates ERR (probe fault), ALR (alarm), DEF (defrost).
Access T1, T2 temps, alarm status; start manual defrost or setup access code.
Access parameter menu using passcode PC 47 via specific buttons.
Parameters adapt controller to system; navigate and change values using buttons.
Displays T1/T2 corrected by offsets OS1/OS2; selectable Celsius/Fahrenheit via SCL.
Compares T1 to setpoint SP and hysteresis HYS for heating/cooling control.
Displays ERR, controls output with fixed time based on CDC parameter.
Automatic start based on DFR timer; manual start via Info Menu.
Controls compressor, fans, and defrost relay based on DTY parameter.
Terminates by DTO time or DLI temp; includes DRN phase for ice melting.
Fans cycle based on FRC parameter, proportionate to compressor run time.
If DS=YES, fans stop immediately upon door opening.
Fans re-start when evaporator temperature is below FDR.
ATL/ATH define alarm differentials for low/high temperatures.
Door alarm enabled by DS=YES; condenser clean warning via ACL parameter.
Displays alarm codes (AH, AL, AD, etc.); mute buzzer with button, relay stays active.
Control lights manually or via door switch (DS, LDC=YES); RS485 for supervisory software.
Secure unit with screws/rivets, protect from liquid infiltration.
Connect probes and power supply per board indications; respect mechanical polarity.
Insert the front panel into the unit and secure with screws.
T1 for air temperature, T2 for evaporator temperature at maximum frost growth.
Operates between -10°C to +50°C; avoid placing signal cables near power lines.
OFF is displayed; [0/1] button enables standby if parameter OFF=YES.
Shows air temp; indicates ERR (probe fault), ALR (alarm), DEF (defrost).
Access T1, T2 temps, alarm status; start manual defrost or setup access code.
Access parameter menu using passcode PC 47 via specific buttons.
Parameters adapt controller to system; navigate and change values using buttons.
Displays T1/T2 corrected by offsets OS1/OS2; selectable Celsius/Fahrenheit via SCL.
Compares T1 to setpoint SP and hysteresis HYS for heating/cooling control.
Displays ERR, controls output with fixed time based on CDC parameter.
Automatic start based on DFR timer; manual start via Info Menu.
Controls compressor, fans, and defrost relay based on DTY parameter.
Terminates by DTO time or DLI temp; includes DRN phase for ice melting.
Fans cycle based on FRC parameter, proportionate to compressor run time.
If DS=YES, fans stop immediately upon door opening.
Fans re-start when evaporator temperature is below FDR.
ATL/ATH define alarm differentials for low/high temperatures.
Door alarm enabled by DS=YES; condenser clean warning via ACL parameter.
Displays alarm codes (AH, AL, AD, etc.); mute buzzer with button, relay stays active.
Control lights manually or via door switch (DS, LDC=YES); RS485 for supervisory software.