6.6 Control Strategy
These trim strategies have been developed and optimised especially for the conditions obtain-
ing in combustion installations:
Frequent changes in the burner-firing rate
Long dead times.
During burner start-up, O
2
trim remains in standby, until it is ensured that plausible measured
O
2
values are displayed.
Factory setting: 90 seconds after ignition - parameter 904 (adjustable).
The "neutral value” is output during standby.
The neutral value depends on the selected correction mode;
e.g. in the case of -50% to +50%, the correction value (neutral value) output is 500; in the case
of -30% to +70%, the output value is 300.
NOTICE
The neutral value corresponds to the base settings of the ETAMATIC without control.