24
3 System Operation
750 Shut-down on faults via bus.
751** No data transfer via the bus (time-out).
759 Operating mode ADJUSTMENT did exceed the time limit of 24 hrs
760 Change of curve selection during setting not allowed G3
761 Change of curve lasts too long
763 Different curve selection between the processors
764 CO-Controller, internal fault no. -
765 Parameter setting error: The channel for solo-fuel is not to determine.
766 The limited load (maximum load without additional-fuel) does not exist in the
priority curves.
767 One parameter of the interpolation type for the non-fuels is invalid.
768 The curve-set-variable for the assigned air channel (1-priority 2-additional
curve) is invalid.
769 Ignition while mixed fuel operation or burner-start with solo-fuel-A
770 Fill-Time for fuel-A to long
791** Bus master is in stop.
792** Bus data length incorrectly configured.
793** Bus master is decoupled.
800 Error in parameters, for parameter no.: A7, A9,
A14
888 Fault block activated!
889 Remote-fault-reset happens within a too short distance
900 Error in self-test sequencer. A7
901 Terminal 10 +24 Volt switch-off faulty. A7, A21,
A22
902 Error in overvoltage self-test. A7
903 Error in optical coupler self-test. A7,G7
904* Error in reference of load A7,A21
905* Error in reference element of main processor A7,A21
906* Error in reference element of monitoring processor A7,A21
907 Curve set adjustment via Lamtec System Bus, self-test recognizes fault
911* Error in reference, channel: 1 A7,A21
912* Error in reference, channel: 2 A7,A21
913* Error in reference, channel: 3 A7,A21
914* Error in reference, channel: 4 A7,A21
915* Error in reference, channel: 5 A7,A21
921 Relay driver self-test: output terminal 11 or 66 (ETAMATIC) faulty. A19,A7
922 Relay driver self-test: output terminal 16 or 65 (ETAMATIC) faulty. A19,A7
923 Relay driver self-test: output terminal 43 or 68 (ETAMATIC) faulty. A19,A7
924 Relay driver self-test: output terminal 67 faulty. A19,A7
925 Relay driver self-test: output terminal 45 faulty. A19,A7
926 Relay driver self-test: output terminal 68 or 61 (ETAMATIC) faulty. A19,A7
927 Relay driver self-test: output terminal 36 (ETAMATIC K202) faulty. A19,A7
Aids FMS Aids ETA