3 System Operation
141 Potentiometer faulty, feedback changing too quickly: channel 1 E13
142 Potentiometer faulty, feedback changing too quickly: channel 2 E13
143 Potentiometer faulty, feedback changing too quickly: channel 3 E13
144 Potentiometer faulty, feedback changing too quickly: channel 4 E13
145 Potentiometer faulty, feedback changing too quickly: channel 5 E13
151** Recirculation damper deactivated, out of time in reaching CLOSED position,
channel: 1
E2,B1,B3
152** Recirculation damper deactivated, out of time in reaching CLOSED position,
channel: 2
E2,B1,B3
153** Recirculation damper deactivated, out of time in reaching CLOSED position,
channel: 3
E2,B1,B3
154** Recirculation damper deactivated, out of time in reaching CLOSED position,
channel: 4
E2,B1,B3
155** Recirculation damper deactivated, out of time in reaching CLOSED position,
channel: 5
E2,B1,B3
161** Monitoring direction of rotation: channel 1 E2,E17
162** Monitoring direction of rotation: channel 2 E2,E17
163** Monitoring direction of rotation: channel 3 E2,E17
164** Monitoring direction of rotation: channel 4 E2,E17
165** Monitoring direction of rotation: channel 5 E2,E17
171** Dead band over range too long: channel 1 B1,B4,E2,
E4,E5
172** Dead band over range too long: channel 2 B1,B4,E2,
E4,E5
173** Dead band over range too long: channel 3 B1,B4,E2,
E4,E5
174** Dead band over range too long: channel 4 B1,B4,E2,
E4,E5
175** Dead band over range too long: channel 5 B1,B4,E2,
E4,E5
181** Dead band under range too long: channel 1 B1,B4,E2,
E4,E5
182** Dead band under range too long: channel 2 B1,B4,E2,
E4,E5
183** Dead band under range too long: channel 3 B1,B4,E2,
E4,E5
184** Dead band under range too long: channel 4 B1,B4,E2,
E4,E5
185** Dead band under range too long: channel 5 B1,B4,E2,
E4,E5
191* 1st monitoring band over range too long: channel 1 B1,B3
192* 1st monitoring band over range too long: channel 2 B1,B3
193* 1st monitoring band over range too long: channel 3 B1,B3
194* 1st monitoring band over range too long: channel 4 B1,B3
195* 1st monitoring band over range too long: channel 5 B1,B3