3 System Operation
363 Permissible O
2
value was fallen below
370 Internal communication between the processors faulty A20
371 Output for internal load faulty C4
372 Deviation between main processor and monitoring processor load values too
great
381 Deviation between main processor and monitoring processor too great: cor-
rection channel 1
A7,F6
382 Deviation between main processor and monitoring processor too great: cor-
rection channel 2
A7,F6
391 Curves sentence does not fit to the chosen fuel. A7,A19
392 Remote not responding (time-out)
393 Remote shut down triggered
394 BURNER-ON/OFF remote signal missing
400 Different point number at programming A23
451 * Ignition position was left in ignition mode. Channel: 1 E18
452 * Ignition position was left in ignition mode. Channel: 2 E18
453 * Ignition position was left in ignition mode. Channel: 3 E18
454 * Ignition position was left in ignition mode. Channel: 4 E18
455 * Ignition position was left in ignition mode. Channel: 5 E18
500 Internal comparison: relay output terminal 67 not picking up. A19,A7
501 Internal comparison: relay output terminal 43 or 68 (ETAMATIC) not picking
up.
A19,A7
502 Internal comparison: relay output terminal 16 or 65 (ETAMATIC) not picking
up.
A19,A7
503 Internal comparison: relay output terminal 11 or 66 (ETAMATIC) not picking
up.
A19,A7
504 Internal comparison: relay output terminal 45 not picking up. A19,A7
505 Internal comparison: relay output terminal 68 or 61 (ETAMATIC) not picking
up.
A19,A7
506 Internal comparison: relay output terminal 36 (ETAMATIC K202) not picking
up.
A19,A7
507 Internal comparison: relay output terminal 41 not picking up. A19,A7
508 Internal comparison: relay output terminal 76 not picking up. A19,A7
509 Internal comparison: Output K203 not picking up.
510 Internal comparison: Output K201 not picking up.
520 Internal comparison: relay output terminal 67 not dropping out. A19,A7
521 Internal comparison: relay output terminal 43 or 68 (ETAMATIC) not dropping
out.
A19,A7
522 Internal comparison: relay output terminal 16 or 65 (ETAMATIC) not dropping
out.
A19,A7
523 Internal comparison: relay output terminal 11 or 66 (ETAMATIC) not dropping
out.
A19,A7
524 Internal comparison: relay output terminal 45 not dropping out. A19,A7
525 Internal comparison: relay output terminal 68 or 61 (ETAMATIC) not dropping
out.
A19,A7
Aids FMS Aids ETA

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals