63
4 Appendix
Voltage supply 230 V + 10% - 15% 50/60 Hz
To be used only in a grounded power line network!
Power input approx. 34 VA
Ambient temperature
Operation: + 0° C…+ 60° C
Transport and
Storage
- 25° C…+ 60° C
Display Alphanumeric display, 16-digit switchable to set-point, load rating, status, actual value feed-
back, set-point feedback, digital inputs, continuous control output value, correction input
and correction range. Running text display
Admissible ambient
humidity
Class F, DIN 40 040
Inputs and outputs 16 Digital inputs
8 - 16 Digital inputs
1 - 5 Analog outputs
12 Analog outputs
all carrying a potential
Digital signal inputs 16 via floating 24 V DC contact, or optionally via 230 V module, type 6 60 R 0018
The parasitic capacitance of the 2,2 µF line connected to the digital inputs must not be
exceeded by the FMS self-tests. The line length should be limited to 100 m.
Load default Either potentiometer 1 - 5 k current signal (0/4 ... 20 mA) or
three-point step control output
Optional: PT 100 direct switching
Feedback inputs Either potentiometer 1 - 5 k current signal (0/4 ... 20 mA)
Optional: Namur transmitter direct switching
Control outputs 4 or 5 either continuous or three-point step, on FMS 5 channel 5 fixed continuous.
Resolution
each analog input
999 points, 10 bit
Three-point step
Recommended run-
ning time of servo
drives
30 s…60 s

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals