32
6 Commissioning
The symbol appears in the status line.
The probe heats up (approx.10 min.).
LD 603 green OPERATION lights up.
COLD START is displayed.
The cold start serves to suppress incorrect measured values while the probe is heating
up. A cold start delay is always activated after MAINS ON and a fault reset. Premature
termination via the CALIBRATION menu possible (see Chapter 6.3.4 Premature Cold
Start Termination).
After a concluded COLD START (approx. 10 minutes), the device switches to measuring
mode.
The probe voltages U-O
2
and U-CO
e
stabilise to values between +10 ... -20 mV.
The internal resistances of the sensor R
ki
O
2
and R
ki
CO stabilise to values between
15 ... 25 .
For the analogue outputs, a replacement value can be set via the LSB remote software while
the maintenance mode is active.
Parameter 2035 and Parameter 2042 for analogue output 1
Parameter 2075 and Parameter 2082 for analogue output 2
WARNING!
Danger of burns!
Probe becomes hot during operation.
If the probe is operated when removed, there is a danger of burns on the probe housing.
Never lay the probe on flammable material and heat it up.
Wear protective gloves
Wait for transmission end indication.
Return to the SETTINGS menu with the
BACK and repeat the procedure.
In case of cancelling or timeout, this display
appears. Return to the SETTINGS menu
with the BACK .

Table of Contents

Other manuals for Lamtec KS1D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec KS1D and is the answer not in the manual?

Lamtec KS1D Specifications

General IconGeneral
BrandLamtec
ModelKS1D
CategoryTransmitter
LanguageEnglish

Related product manuals