16
4 Mounting and Functions
4.2 Connection Extension
Extension via probe terminal box
In preparation.
Extension via extension cable
For distances > 2 m, extension cables in lengths of 2 m and 5 m are available.
NOTICE
The maximum distance between LT3-F and combination probe KS1D may not exceed 10 m.
With longer distances the approval of the system for continuous operation expires.
For distances longer than 10 m the risk of EMC increases.
LAMTEC assumes no responsibility for correct, error-free functions.