36
6 Commissioning
The R
ki
internal probe resistance values
lie between 15 ... 25 .
Display of whether the internal probe
resistance regulation is active!
P
h
Display of the current heating capacity
R
ki
S Display of the setpoint value for the
internal resistance regulation.
O
2
-CO: Evaluates the cross-talk response
between the O2 and CO electrodes.
If the influence is too large (>15 %), the sen-
sor signals overwrite each other. This leads
to measurement faults and triggers Fault
FH007/10 after 30 seconds. A basic influ-
ence always exists due to the common GND
of the electrodes.
Currently selected fuel.