EasyManua.ls Logo

Lamtec LT3-F - Reading the Measured Values

Lamtec LT3-F
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
6 Commissioning
6.3.5 Reading the Measured Values
In the main menu, select the INFORMATION
menu with .
In the INFORMATION menu, select meas-
ured values and probe data with .
In measured values and probe data, select:
Display of the O
2
measured values
Display of the CO
e
measured values
Display of the R
ki
internal probe
resistances
Display of the current fuel
selection
The O
2
probe voltage U-O
2
stabilises to val-
ues between +10 ...-20 mV.
The CO probe voltage U-CO stabilises to
values between +10 ...-20 mV.

Table of Contents

Related product manuals