Bulletin Number: 20031201 Rev A S4e-UtiliNet User Manual Page 12 of 13
Technical Features of the S4e UtiliNet
S4e and UtiliNet Specifications
Applicable Standards
ANSI C12.1-2001 for electricity metering
ANSI C12.10-1987 for watt-hour meters
ANSI C12.20-1998 for solid-state electricity meters
CAN3-C17-M84 Canadian Specs for approval of electrical meters
CAN3-Z234.4-79 Canadian Specs for all-numeric dates and times
FCC Certified Part 15.247
Industry Canada RSS 210
NOM 121-SCTI-1994
Application Information
Frequency 50 or 60 Hz +/- 5%
Nominal Voltage 120-480 VAC ranging
Operating Voltage 80-115% of nominal
Operating Temperature
Meter -40 to +85 C under cover
UtiliNet Radio -40 to +60 C under cover
Humidity Meter Less than or equal to 95% relative humidity, non-condensing
UtiliNet rated 65
0
C at 90% relative humidity, non-condensing
Meter
Rated Accuracy at Unity Power Factor
Transformer-Rated/
Self Contained Meters +/- 0.2%
K-Base Meters +/- 0.5%
Over voltage Withstand
Temporary (.5 sec) 150% rated voltage
Continuous (5 hours) 120% rated voltage
Starting Load:
Class 20 0.004 amps
Class 200 0.050 amps
Class 320 0.050 amps
Available Meter Forms
Base Transformer Rated
Class 20
Class 120 Class 200 Class 320** Class 480
S-Base 3, 9/8, 45(5)*,
36(6)*, 29, 56
2, 12, 25,
16/15/14
2, 12, 16/15/14
A-Base 10/8, 45(5)*, 36(6)* 16/15/14
K-Base 12, 16/15/14,
and 27
*36S/36A replaces the traditional 6S/6A, 45S/45A replaces the traditional 5S/5A
**Class 320 Meters are referred to as SE base