Terminal6 - 230 Vac motor M2 power supply phase (opening)
Terminal7 - 230 Vac motor M2 power supply phase (closure)
Terminal8 - 230 Vac motor M2 Power supply common
Note: connect the capacitor of the motor M2 between terminals 6 and 7
Terminal9 - 230 Vac blinker power supply phase
Terminal10 - 230 Vac blinker power supply neutral
Terminal board J6
Terminal1 – Electric lock 12 Vac power supply
Terminal2 – Electric lock 12 Vac power supply (common)
Terminal3 – 24 Vac power supply for photo-cells or other devices (common)
Terminal4 – 24 Vac power supply for photo-cells or other devices
Terminal5 – Common terminal for all electric contacts of commands or security devices
Terminal6 – Photo-cell’s normally closed electric contact
Terminal7 – Emergency push-button’s normally closed electric contact (stop)
Terminal8 – Photoelectric cell’s normally closed electric contact (photostop)
Terminal9 – Start push-button’s normally open electric contact
Terminal10– Pedestrian start push-button’s normally open electric contact
Important: The normally closed inputs not in use must be fitted with jumpers
Terminal board J4
Terminal1 – 2nd radio-channel’s normally open electric contact (output)
Terminal2 – 2nd radio-channel’s normally open electric contact (output)
Terminal3 – Aerial cable connection (shield) for radio receiver card
Terminal4 - Aerial cable connection (signal) for radio receiver card
Terminal board J7
Terminal1 – Courtesy light’s or electric chain’s 230 Vac power supply phase
Terminal2 – Courtesy light’s or electric chain’s 230 Vac power supply neutral
Connector J3
Terminal1 – 230 Vac motors M1 and M2 Power supply common
Terminal2 – 230 Vac motors M1 and M2 Power supply common
Terminal3 – 230 Vac motors M1 and M2 Power supply common
Terminal4 – 230 Vac mains power supply neutral
Important
: If the power regulator card is not connected the J3 connector’s terminals 3 and 4 must be bridged with 4 mm insulated faston
terminal.