EasyManua.ls Logo

LECTRO 36VDC - Connecting an Additional 48 V Battery String; Connecting an Additional 36 V Battery String

Default Icon
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
3.0 Power Supply, continued
745-573-B0-001 REV. A
3.2 Battery Installation and Connection, continued
3.2.3 Connecting an Additional 48V Battery String
NOTE: This procedure assumes that the additional battery string is being installed in a
Lectro brand cabinet.
1. Confirm the CPR
TM
DC circuit breaker is off (down).
2. Place the batteries in the bottom of the cabinet with the negative terminals (-) at the rear of the
cabinet.
3. Connect the red battery lead from the lower shelf at the positive (+) terminal of the left battery.
Torque connection to 60 inch-pounds (6.8 Newton-meters).
4. Disconnect the red battery lead cable from the upper shelf at the positive (+) terminal of the left
battery. Reconnect this lead with the red lead of the inter-shelf connection cable.
5. Connect the three (3) battery interconnection jumpers as shown below. Torque all
connections to 60 inch-pounds (6.8 Newton-meters).
6. Disconnect the black battery lead cable from the upper shelf at the negative (-) terminal of the
right battery. Reconnect this lead with the black lead of the inter-shelf connection cable. Torque
connection to 60 inch-pounds (6.8 Newton-meters).
7. Measure the DC voltage to ensure proper installation of all battery wiring. Open circuit DC voltage
should measure at least 48 volts across both parallel strings.
8. Verify the gray Anderson connector is properly attached to the left side of the CPR module.
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
UPPER
SHELF
LOWER
SHELF
CABINET FRONT
RED
BLACK
Fuse
Fuse
Gray Anderson
Connector
Fig. 3-7, 48V Battery Connections – parallel strings P/N 875-183-20