Controller - 1 x 1000 W output with
dimming - All loads
CONTENTS
1. USE
This device is a power unit used for managing lighting loads.
The load(s) can be controlled locally either manually or by SCS
commands associated with it (them). They can also be controlled
automatically by digital detectors.
The use of SCS commands and digital detectors requires an SCS
power supply and an addressing module* to be wired on the
BUS.
* The addressing module is not necessary if the installation is
equipped with the software packs.
2. TECHNICAL FEATURES
CONTENTS Page
1. Use ............................1
2. Technical features ................1
3. Overall dimensions................2
4. Connection ......................2
5. Parameter setting .................3
6. Operation .......................3
7. Maintenance.....................3
8. Standards .......................3
230 V~ 1000 W
4.3 A
1000 W
4.3 A
1000 VA
4.3 A
1000 VA
4.3 A
110 V~ 500 W 500 W 500 VA 500 VA
1 2 3 4
1
Incandescent bulbs
2 Tungsten halogen bulbs
3 Tungsten halogen bulbs with ferromagnetic transformer
4 Tungsten halogen bulbs with separate electronic transformer
Number of supply terminal blocks 1
Number of load terminal blocks 1
Connection terminals
Terminal types screw
Terminal capacity 2 x 2.5 mm
2
Number of RJ 45 1
Mains voltage 100-240 V~
Frequency 50/60 Hz
Location category Internal
Degree of protection
Penetration by solid
and liquid matter
IP20
(installation in an enclosure)
Impact resistance IK04
Number of modules 6
Usage temperature -5°C to +45°C
Storage temperature -20°C to +70°C
No load power consumption 0.3 W
Weight 327 g
2. TECHNICAL FEATURES (continued)
LEARN indicator:
indicates the teach
phase or RESET
Indicator
(on if output
activated)
Configurator
Control
button
LEARN button
SCS BUS connection
(RJ 45)
CAUTION:
Do not combine on
the same channel
3
+
4
Only one transformer for use with an electronic switch must be used.
Question and Answer IconNeed help?

Do you have a question about the LEGRAND 026 21 and is the answer not in the manual?

Summary

Product Use and Application

Device Technical Specifications

BUS Wiring Details

Details on BUS wiring requirements including cable type and length.

Compatible Peripherals

Lists compatible digital detectors, pushbuttons, and scenario management devices.

Overall Dimensions and Layout

Electrical Connection Guide

Parameter Setting Configuration

Device Operation and Load Control

Manual Load Type Forcing

Instructions for manually forcing the load type for the device.

Maintenance and Cleaning Procedures

Applicable Standards and Regulations

Overview

This document describes the Legrand Controller, specifically model 026 21, a 1 x 1000 W output device with dimming capabilities, designed for all load types. It is a power unit primarily used for managing lighting loads within a building automation system.

Function Description

The controller allows for versatile control of lighting loads. It can be operated locally, either manually via integrated buttons or through SCS (Simplified Control System) commands. Additionally, it supports automatic control via digital detectors. For SCS commands and digital detectors to function, an SCS power supply and an addressing module are required to be wired on the BUS. However, the addressing module is not necessary if the installation utilizes software packs. The device features a configurator for setup, a LEARN indicator to show the teach phase or RESET status, and a LEARN button for configuration. It also includes an indicator to show if the output is activated.

Important Technical Specifications

  • Catalogue Number: 026 21
  • Supply Terminal Blocks: 1
  • Load Terminal Blocks: 1
  • Connection Terminals: Screw type, 2 x 2.5 mm² capacity
  • RJ 45 Ports: 1
  • Mains Voltage: 100-240 V~
  • Frequency: 50/60 Hz
  • Location Category: Internal
  • Degree of Protection:
    • Penetration by solid and liquid matter: IP20 (suitable for installation in an enclosure)
    • Impact resistance: IK04
  • Number of Modules: 6
  • Usage Temperature: -5°C to +45°C
  • Storage Temperature: -20°C to +70°C
  • No Load Power Consumption: 0.3 W
  • Weight: 327 g
  • Load Capacity (at 230 V~):
    • Incandescent bulbs: 1000 W (4.3 A)
    • Tungsten halogen bulbs: 1000 W (4.3 A)
    • Tungsten halogen bulbs with ferromagnetic transformer: 1000 VA (4.3 A)
    • Tungsten halogen bulbs with separate electronic transformer: 1000 VA (4.3 A)
  • Load Capacity (at 110 V~):
    • Incandescent bulbs: 500 W (4.3 A)
    • Tungsten halogen bulbs: 500 W (4.3 A)
    • Tungsten halogen bulbs with ferromagnetic transformer: 500 VA (4.3 A)
    • Tungsten halogen bulbs with separate electronic transformer: 500 VA (4.3 A)
    • Note: Only one transformer should be used with an electronic switch.

Overall Dimensions:

The device measures 108 mm in width, 83 mm in height, and 66 mm in depth, with a mounting depth of 50 mm and a total depth of 45 mm from the front face.

BUS Wiring:

The controller connects via an RJ 45 cord or cable, or a BUS/SCS cable, fitted with an RJ 45 connector. The maximum cord or BUS/SCS cable length between the power supply and the furthest product is 500 meters.

Compatible Peripherals:

The controller is compatible with various Legrand peripherals, including:

  • Digital detectors (infrared, ultrasound, or dual technology)
  • Pushbutton lighting controls
  • Switch multifunction controls
  • Scenario management

Usage Features

Connection:

All wiring must be performed with the mains power off. The connection diagrams illustrate how to wire the controller to different phases (L1, L2, L3) and neutral (N) for various load types.

Parameter Setting:

The product can be configured in a system using several methods:

  • Manual: Using the Push and Learn method.
  • Virtual: Via software packs.
  • Physical: Via configurators. Detailed parameter setting for compatible digital detectors can be found in their respective technical data sheets. All technical information is available on www.legrandoc.com.

Operation:

By default, the product automatically recognizes the connected load as soon as the channel is activated. If automatic recognition fails, this function can be manually forced.

Display of Load Type and Status:

The device includes indicators for both load status and load type.

  • Load Status Indicator: Displays the status of load 1.
    • Off: Load is OFF.
    • On: Load is ON (1% to 100%).
    • Flashing: Load short-circuit fault.
  • Load Type Indicator: Indicates whether the load is Inductive or Capacitive.

Manual Forcing of Load Type:

This feature allows users to manually set the load type.

  1. Press the RL/C button for less than 1 second to enter forcing mode.
  2. Press ON/+ for less than 1 second to select "Capacitive" or "Forced capacitive."
  3. Press OFF/- for less than 1 second to select "Inductive" or "Forced inductive."
  4. To confirm the selection, press the RL/C button for 10 seconds.
  5. To exit forcing mode without saving, press the RL/C button for less than 1 second.

Control Buttons:

The device features ON/+ and OFF/- buttons for load control:

  • ON/+ command:
    • Short press: Turns ON the load.
    • Long press: Dims up (Dim+).
  • OFF/- command:
    • Short press: Turns OFF the load.
    • Long press: Dims down (Dim-).

Standards:

The product complies with the following standards and directives:

  • Directive: CE
  • Installation Standards: NFC 15-100
  • Product Standards: IEC 60669-2-1
  • Environmental Standards:
    • EU Directive 2002/96/EC (WEEE - Waste Electrical and Electronic Equipment)
    • EU Directive 2002/95/EC (RoHS - Restriction of Hazardous Substances)
  • Regulations:
    • ERP (public buildings)
    • ERT (workplace buildings)
    • IGH (high-rise buildings)

Maintenance Features

Cleaning:

  • Do NOT use: Acetone, tar-removing cleaning agents, or trichloroethylene.
  • Recommended cleaning products:
    • Hexane (EN 60669-1)
    • Methylated spirit
    • Soapy water
    • Diluted ammonia
    • Bleach diluted to 0%
    • Window-cleaning products
  • ATTENTION: An initial test is required before using any other special maintenance products.

LEGRAND 026 21 Specifications

General IconGeneral