EN
19
Niky 1000/1500
9 Technical features
CONSTRUCTION SPECIFICATIONS
3 100 04
3 100 13
3 100 26
3 100 05
3 100 14
3 100 27
Weights 13 Kg. 16 Kg.
Dimensions L x H x P in mm 147 x 239 x 354
Protection
Electronic protection against overloading
and short-circuiting. Shutdown on
reaching operating limit and overheating.
Automatic shutdown due to protection
triggering
Ambient specifications
Operating temperature range from 0 to +40 °C
Operating relative humidity range from 0 to 95% non-condensing
Degree of protection as per IEC529 IP20
Noise level at 1 meter < 40 dBA
Electrical input specifications
Rated input voltage 230 V
Range of input voltage 175-285VAC
Rated input frequency 50-60 Hz +/-5Hz
Maximum input current 6,2 Arms 8,5 Arms
Number of input phases Single phase
Waveform on output
With battery operation step wave
Type of operation line interactive
Electrical specifications on output
Rated output voltage 230 V ± 10 %
Output current on nominal load 4,7 Arms 6,5 Arms
Apparent output capacity on nominal load 600 W 900 W
Apparent output capacity on nominal load 1000 VA 1500 VA
Overload capacity 110% for 5 s.
Number of phases on output Single phase