1. General features
The automatic transfer switch has been designed for switching applications between two power sources (power grids or
generators). ATS has an LCD screen to provide a clear and intuitive user interface.
1.1 Description
128x80 pixel, backlit LCD screen with 4 grey levels.
5 keys for functions and setting.
4 LEDs for plant synoptic (source line and breakers status).
2 LEDs for alarm presence and AUTO mode active.
5-language text for measurements, settings and messages.
Programmable I/O functions.
Fully user-definable alarm properties.
Line 1: 3-phase + neutral voltage reading input (S.Q1).
Line 2: 3-phase + neutral voltage reading input (S.Q2).
100-240VAC power supply.
Voltage thresholds with programmable hysteresis.
Front optical programming interface, galvanically isolated, which can be connected with USB and WiFi dongles.
6 programmable digital inputs (negative).
6 + 1 outputs:
- 6 relays with NO contact 8A 250VAC.
- 1 relay with changeover contact 8A 250VAC.
IP 40 front protection.
Compatible with App and SW ACU.
1.2 Applications
To check and to manage lines (line-to-line (U-U), line-generator (U-G) or generator-generator (G-G)).
Control of motorized circuit breakers or contactors.
Control of voltage source for three-phase, two-phase or single-phase systems.
Control of phase-phase and / or phase-neutral voltages.
Controls of undervoltage, overvoltage, phase loss, asymmetry, minimum frequency, maximum frequency.
1.3 Installation
Install the unit following the instruction sheet attached to the product. Evaluate if the default configuration is in com-
pliance with the desired one. Otherwise it is necessary modify the configuration. Check the wiring diagram supplied by
Legrand in order to correctly connect the unit and others Legrand devices.
The ATS standard configuration guarantees the correct work of devices if wiring diagrams supplied are respected.
WARNING
The change of parameters, of input functions, of output functions etc... causes a functional change. This could cause
incompatibility with standard wiring diagrams. It is recommended to evaluate changes of parameters or functional
modes after having read the ATS user manual.
At first power on, the OFF/RESET mode is activated on the ATS.