EasyManua.ls Logo

LEGRAND Inform SINUS EVO - Output Voltage Setting

LEGRAND Inform SINUS EVO
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
01: Output Voltage Setting
Interface
Setting
Parameter 3: Output voltage
For 208/220/230/240 VAC models, you may choose the following output
voltage:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For 110/150/120/127 VAC models, you may choose the following output
voltage:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac
02: Frequency Converter Enable/Disable
Interface
Setting
Parameter 2 & 3: Enable or disable converter mode. You may choose the
following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable(Default)
03: Output Frequency Setting
Interface
Setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following output
frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
04: ECO Enable/Disable
Interface
Setting
Parameter 3: Enable or disable ECO function. You may choose the
following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)