15
05: ECO Voltage Range Setting
Interface
Setting
Parameter 2 & 3: Set the acceptable high voltage point and low voltage
point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in parameter 3 is
from +7V to +24V of the nominal voltage.
(Default: +12V)
For 110/115/120/127 VAC models, the setting range in parameter 3 is
from +3V to +12V of the nominal voltage.
(Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in parameter 3 is
from -7V to -24V of the nominal voltage.
(Default: -12V)
For 110/115/120/127 VAC models, the setting voltage in parameter 3 is
from -3V to -12V of the nominal voltage.
(Default: -6V)
06: Bypass Enable/Disable When UPS İs Off
Interface
Setting
Parameter 3: Enable or disable Bypass function. You may choose the
following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass Voltage Range Setting
Interface
Setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable low
voltage point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 208/220/230/240 VAC models:
235-264: setting the high voltage point in parameter 3 from 235Vac to
264Vac. (Default: 264Vac)
For 110/115/120/127 VAC models:
125-132: setting the high voltage point in parameter 3 from 115Vac to
132Vac(Default: 132Vac)
LLS: Bypass low voltage point
For 208/220/230/240 VAC models:
184-225: setting the low voltage point in parameter 3 from 184Vac to
225Vac. (Default: 195Vac)
For 110/115/120/127 VAC models:
98-115: setting the low voltage point in parameter 3 from 98Vac to
115Vac. (Default: 98Vac)