31
KEOR T
Installation Manual
If the batteries are already built-in inside the UPS cabinet; in order
to avoid any danger during transportation, some battery connec-
tions are left unconnected.
Thus, remove the left & right covers of UPS; disconnect the side
panels’ earth cables. Connect the unconnected battery cables to the related battery connectors. The un-
connected cables are labelled. You may nd detailed information about battery connection as follows.
There is no need any further connection, so reconnect the side panels earth cables and replace the covers.
Please add three-pole (3-pole) MCCB to distribution panel for UPSs auxiliary input.
Danger of explosion and re if the batteries of the wrong type are used.
Battery fast fuses shall only be replaced with fuses of the same type and rating.
Internal Battery Connection:
Do not use internal and external battery together!
If UPS with internal battery; there are no X5, X7 and X8 terminals mounted on the
UPS.
LETHAL VOLTAGE of nominal 720 VDC is present when the external battery con-
nections are made.
The batteries must be charged min. 10 hours before rst-use.
Connect the phase cables to X4 AUXILIARY SUPPLY: X4/L1 - X4/L2 - X4/L3 terminals, the neutral to X4
AUXILIARY SUPPLY: X4/N terminal. Neutral connection should be done directly from distribution neutral
bus to UPS neutral.
5.3.1.4. Battery Connection
You may nd more information about Keor T Models and Battery capacity in Section 5.1. Models and Di-
mensions.
If auxiliary supply exists, remove all bridges.