EasyManua.ls Logo

LenelS2 3 Series - User Manual

Default Icon
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Dual Reader Interface Module LNL-1320 Series 3
Quick Reference
for rev. D and higher (SN > 3,000,000)
For detailed information, refer to the Hardware Installation Guide, DOC-600.
© 2020 Carrier. All Rights Reserved. LenelS2 is a part of Carrier. 1 QR50L-1034E — revision 3.004
The LNL-1320 Board
The LNL-1320 reader interface boards provide a solution to the host system
integrator for interfacing to a TTL (D1/D0, Clock/Data), F/2F, or 2-wire RS-
485 device and door hardware. The LNL-1320 provides a tri-state LED
control and buzzer control. Six (6) Form-C relay outputs may be used for
strike control or alarm signaling. Eight (8) inputs are provided that may be
used for monitoring the door contact, request to exit push button and alarm
contacts. Input circuits can be configured as unsupervised or supervised.
The LNL-1320 communicates to the controller via a 2-wire RS-485.
See the following diagram for component location (some components
shown are not present on the LNL-1320).
Supplying Power to the LNL-1320
The LNL-1320 accepts 12 to 24 VDC for power on TB7 (VIN and GND).
Locate the power source as close to the LNL-1320 as possible. Make power
connection with minimum of 18 AWG wires.
Observe POLARITY on VIN!
The VOUT terminal on TB7 is the same as VIN.
Communication Wiring (SIO Communication Port)
The LNL-1320 communicates to a Lenel intelligent controller (LNL-3300,
for example) via a 2-wire RS-485 interface. The LNL-1320 allows for
multi-drop communication on a bus of up to 4000 feet (1219 m). Use
twisted pair (minimum 24 AWG) with drain wire and shield for
communication. See Specifications section.
Install RS-485 termination jumper, J4, on the interface boards at each end of
the communication line only.
2-Wire RS-485
The LNL-1320 Board Callouts
Callout Description
1 Inputs
2 DC input power
3 Earth ground (connection not required)
4 Eight (8) mounting holes (Ø0.156 [Ø4.0])
5 Output relays
6 DIP switches
7 Reader interface
8 Status LEDs
INPUTS
IN1
IN2
IN3 IN4
TB1
TB2
TB3
IN5
IN6
TB4
IN7 IN8
TB5
TMP
GND
PFL
GND
TR-
NC
NC
GND
TR+
TB6
RS-485
TB7
VIN
GND
VOUT
A
B
1
2
34
5
6 7 8 PFL
R1
R2
TMP
NC NO C NC
RLY 1
CNO
RLY 2
RLY 4 RLY 3
NO CNONCCNC
RLY 6
RLY 5
NO CNONCCNC
TB10
TB11
TB12
READER 2
VO
LED
BZRCLKDATGND
D1
D0
VO
LED
BZRCLKGND
D1
D0
DAT
READER 1
TB8
TB9
12V
PT
J1
K1
K2
K3 K4
K5
K6
J4
1
4
3
2
^
|
ON
1
4
3
2
5
8
7
6
S1S2
.25 [6.35]5.50 [139.70]
6.00 [152.40]
2.00 [50.80]3.00 [76.20]
2.00 [50.80]
8.00 [203.20]
.50 [12.70]
4
5
6
7
1
3
2
8
Communication Wiring (SIO Communication Port) Callouts
Callout Description
1 To all other devices on the bus
2 To all other devices on the bus
ONLY 2-WIRE RS-485 IS SUPPORTED
VIN
GND
+
-
12 to 24 VDC
TB7
VOUT
TR+
TR -
GND
TB6
1
2
NC
NC
Question and Answer IconNeed help?

Do you have a question about the LenelS2 3 Series and is the answer not in the manual?

Summary

The LNL-1320 Board

Supplying Power to the LNL-1320

Details how to connect power to the LNL-1320, accepting 12 to 24 VDC.

Communication Wiring (SIO Communication Port)

Explains RS-485 communication to a Lenel controller via 2-wire interface.

Reader Wiring

Reader Wiring Overview

Covers reader interfaces, cable requirements, and power selection.

Reader Wiring Examples

Illustrates wiring for various reader types including F/2F, D1/D0, and RS-485.

Alarm Contact Wiring

Input Circuit Configurations

Details configurations for unsupervised and supervised alarm inputs.

Inputs for Cabinet Tamper;Power Fault

Cabinet Tamper and Power Fault Monitoring

Explains inputs for monitoring cabinet tamper and power failure.

Output Relay Wiring

Form-C Relay Outputs

Describes the six Form-C relay outputs for door strikes and load switching.

Contact Protection Circuit

Recommends circuits to minimize premature contact failure and EMI.

Jumper and DIP Switch Usage

Jumper Settings

Details jumper functions for reader power select and RS-485 termination.

DIP Switch Functions

Explains DIP switches for device address, baud rate, and encryption.

Status LEDs

LED Status Meanings

Defines meanings for Power, A, B, R1, R2, and K1-K6 LEDs during operation.

Specifications

Electrical Specifications

Lists primary power, output, input, reader interface, and communication specs.

Cable Requirements

Details cable types and lengths for power, RS-485, alarm inputs, and readers.

Mechanical and Environmental

Provides dimensions, weight, temperature, and humidity ratings.

UL 294 Performance Levels

Outlines UL 294 performance levels for Standby Power, Endurance, Line Security, and Destructive Attack.

Regulatory Information

FCC Compliance

States compliance with FCC Part 15 rules for interference.

Liability and Product Warnings

Disclaims liability for misapplication and clarifies product intended use.

Overview

The LNL-1320 Dual Reader Interface Module Series 3 is designed to provide a flexible and robust solution for integrating various reader technologies and door hardware into a host access control system. This module acts as an intermediary, translating signals from readers and door components into a format that can be understood by a central intelligent controller, such as the LNL-3300. Its primary function is to manage access control at a door, supporting a range of reader types and monitoring door status and alarm conditions.

Function Description

The LNL-1320 supports multiple reader technologies, including TTL (D1/D0, Clock/Data), F/2F, and 2-wire RS-485 devices. This versatility allows integrators to choose from a wide array of readers based on their specific security requirements. The module provides power to the readers, with options for either a regulated 12 VDC supply or a pass-through of the input voltage (VIN) from the LNL-1320's main power input. This power selection is configurable via a jumper (J1), offering flexibility in reader power management.

Beyond reader integration, the LNL-1320 is equipped with six Form-C relay outputs. These relays are typically used for strike control, allowing the module to unlock or lock doors based on access decisions made by the intelligent controller. They can also be configured for alarm signaling or other auxiliary functions, providing a versatile output capability. To ensure system reliability and prevent premature contact failure, especially when switching inductive loads like door strikes, the manual recommends using contact protection circuits. These circuits should be located as close to the load as possible to maximize their effectiveness.

The module also features eight input circuits, designed for monitoring various door hardware components and alarm contacts. These inputs can be configured as either unsupervised or supervised. Unsupervised inputs simply report an open or closed contact state, suitable for basic monitoring. Supervised inputs, on the other hand, offer enhanced security by detecting multiple states, including open circuit, shorted circuit, grounded circuit, or foreign voltage, in addition to open and closed. This requires the use of two 1k ohm, 1% resistors at the end of the line, placed close to the sensor, to allow the module to differentiate between these states. This capability is crucial for detecting tampering or faults in the input wiring.

Two additional dedicated inputs are provided for monitoring cabinet tamper and power fault conditions. These inputs are designed for contact closure monitoring only and do not require end-of-line resistors. If these inputs are not used, a short piece of wire must be installed to indicate a safe condition, preventing false alarms.

Communication between the LNL-1320 and the intelligent controller occurs over a 2-wire RS-485 interface. This allows for multi-drop communication on a bus up to 4000 feet (1219 m), using twisted pair wiring with a drain wire and shield for optimal signal integrity. The RS-485 termination jumper (J4) must be installed only on the interface boards at each end of the communication line to ensure proper bus operation.

Usage Features

The LNL-1320 is designed for ease of configuration and monitoring. DIP switches are used to set the device's communication address (switches 1-5) and the communication baud rate (switches 6-7). This allows for straightforward setup of multiple modules on a single RS-485 bus. An additional DIP switch (switch 8) enables downstream encryption, enhancing security for communications with compatible OnGuard systems.

The module incorporates a series of status LEDs that provide visual feedback on its operational status, communication activity, input states, and output relay states. These LEDs are crucial for troubleshooting and verifying proper operation during installation and maintenance. For instance, the A LED indicates heartbeat and on-line status, differentiating between non-encrypted and encrypted communication modes. It also signals error conditions, such as waiting for firmware download. The B LED shows activity on the serial I/O communication port. Dedicated LEDs for each of the eight inputs (IN1-IN8), cabinet tamper (TMP), and power fault (PFL) indicate their respective states, with different flash patterns for inactive, active, and trouble conditions. Reader port LEDs (R1 and R2) flash to indicate data reception or transmission, depending on the reader mode (Clock/Data, D1/D0, RS-485, F/2F). Finally, K1 through K6 LEDs illuminate when their corresponding output relays are energized, providing a clear visual confirmation of output activation.

The reader ports offer tri-state LED control and buzzer control, allowing for direct management of reader indicators and audible feedback. This configuration is managed via the host software, providing centralized control over reader behavior.

Maintenance Features

The LNL-1320's design includes features that simplify maintenance and troubleshooting. The comprehensive set of status LEDs provides immediate visual diagnostics, allowing technicians to quickly identify the source of an issue without needing specialized tools. For example, if a reader is not communicating, the R1 or R2 LED can indicate whether data is being received or transmitted, helping to narrow down the problem to either the reader, wiring, or communication bus. Similarly, input LEDs can quickly show if a door contact or REX button is functioning correctly.

The use of screw terminals for all connections facilitates easy wiring and replacement of components. The modular design, with clearly labeled callouts for inputs, outputs, power, and communication ports, ensures that connections are made correctly and can be easily verified.

The ability to configure input circuits as supervised is a key maintenance feature, as it allows for proactive detection of wiring faults or tampering. If a wire is cut or shorted, the supervised input will report a trouble state, alerting maintenance personnel to an issue before it leads to a security breach or system failure.

The recommendation for contact protection circuits on relay outputs, while primarily a reliability feature, also contributes to reduced maintenance by extending the lifespan of the relays and preventing damage from inductive loads. This minimizes the need for frequent relay replacements.

Overall, the LNL-1320 is designed to be a reliable and manageable component within an access control system, offering robust functionality and clear diagnostic indicators to support both initial setup and ongoing maintenance.

LenelS2 3 Series Specifications

General IconGeneral
Video Inputs32
Hard Drive BaysUp to 8
Operating SystemLinux-based
Video CompressionH.265/H.264
Audio CompressionG.711
Network Interface10/100/1000 Mbps
USB Ports2
Alarm Inputs/Outputs16 inputs / 4 outputs

Related product manuals