EasyManuals Logo

Lennox Allied Air A95UH1D User Manual

Lennox Allied Air A95UH1D
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
507270-03Page 48 of 60 Issue 1917
Table 13.
Burner Orice Conversion Kits at Varying Altitudes
Capacity
0 - 7,500 ft
(0 - 2,286 m)
7,501 - 10,000 ft
(2,286 - 3,048 m)
Natural to LP/
Propane
LP/Propane to
Natural
High Altitude
Natural Burner
Orice Kit
High Altitude
LP/Propane Burner
Orice Kit
All 11K50+ 73W80* 51W01 11K45+
* Conversion requires installation of a gas valve regulator spring which is provided with the gas
conversion Kit.
+ LP Kits include low line pressure switch.
A93 and 92G1 Pressure Switch Requirements at Varying Altitudes
Capacity
0 - 4500 ft
(0 - 1371m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045
No Change 11J09 11J10
070
090
110
135 No Change 11U70 11U68
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure
switch from 0-4500 feet (0-1371 m).
A95 and 95G1 Pressure Switch Requirements at Varying Altitudes
Capacity
0 - 4500 ft
(0 - 1371m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045 No Change No Change 11J09
070 No Change 11J12 10U93
090 No Change 11U70 10U93
110 No Change 11J12 10U93
135 No Change 11U70 10U93
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure
switch from 0-4500 feet (0-1371 m).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Allied Air A95UH1D and is the answer not in the manual?

Lennox Allied Air A95UH1D Specifications

General IconGeneral
BrandLennox
ModelAllied Air A95UH1D
CategoryFurnace
LanguageEnglish

Related product manuals