507270-03 Page 51 of 60Issue 1917
Blower Performance A93UH1D / 92G1UH
A93UH1D / 92G1UH 045*B08 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High Medium-High Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1140 455 920 365 765 295 710 265
0.10 1135 445 900 360 765 290 690 255
0.20 1125 430 895 350 755 285 680 255
0.30 1090 415 870 340 725 280 660 250
0.40 1065 405 870 325 715 270 635 245
0.50 1020 390 825 315 675 260 605 235
0.60 945 365 780 300 640 250 555 225
0.70 910 350 740 295 585 240 505 220
0.80 790 325 670 275 510 225 455 205
0.90 735 310 575 255 460 220 390 195
A93UH1D / 92G1UH 045*B12 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High Medium-High Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1600 700 1370 590 1160 475 1005 400
0.10 1600 685 1355 565 1155 465 1015 390
0.20 1550 650 1330 540 1150 445 1000 380
0.30 1480 625 1295 515 1140 430 975 365
0.40 1425 590 1280 490 1105 415 975 350
0.50 1355 565 1190 460 1085 695 940 335
0.60 1320 545 1165 435 1030 375 900 315
0.70 1225 500 1110 425 975 355 855 310
0.80 1135 480 1050 395 920 330 780 280
0.90 1025 445 950 360 800 295 700 255
A93UH1D / 92G1UH 070*B08 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High Medium-High Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1140 455 920 365 765 295 710 265
0.10 1135 445 900 360 765 290 690 255
0.20 1125 430 895 350 755 285 680 255
0.30 1090 415 870 340 725 280 660 250
0.40 1065 405 870 325 715 270 635 245
0.50 1020 390 825 315 675 260 605 235
0.60 945 365 780 300 640 250 555 225
0.70 910 350 740 295 585 240 505 220
0.80 790 325 670 275 510 225 455 205
0.90 735 310 575 255 460 220 390 195
NOTE: All air is measured external to unit without lter (lter not furnished - eld provided)