0650329-56 / 506265-03Issue 1924Page 4 of 13
Condensate Drain Connection
Do not operate unit without a drain trap. The condensate 
drain is on the negative pressure side of the blower; 
therefore, air being pulled through the condensate line 
will prevent positive drainage without a proper trap.
To avoid drain pan overow, the web must be removed 
from inside any threaded drain pan hole to which a 
drain line is to be connected. Use care when removing 
the web so as to not damage the coil.
On horizontal units, the primary drain connection is ush 
with the bottom of the inside of pan. Auxiliary connection 
is raised above the bottom of the inside of the pan. Plastic 
web  covering  3/4”  auxiliary  connection  must  be  broken 
out if used. Do not get primary and auxiliary connections 
interchanged.
When  making  drain  tting  connections  to  the  drain  pan, 
hand  tighten  only.  Overtightening  the  ttings  can  split 
connections on the drain pan.
The  unit  is  provided  with  3/4”  FPT  condensate  drain 
connections.
•  Connect the drain lines to the appropriate drain pan 
ttings.
•  Secondary drain connections should be connected to 
a separate drainage system.
•  Install a trap in the drain line below the bottom of the 
drain pan and pitch the drain lines down from the coil at 
least 1/4” per foot of run. Horizontal runs over 15’ long 
must also have an anti-siphon air vent (stand pipe), 
installed ahead of the horizontal run. An extremely 
long horizontal run may require an oversized drain line 
to eliminate air trapping.
•  Route to the outside or to an appropriate drain. Check 
local codes before connecting drain line to an existing 
drainage system.
•  Insulate drain lines where sweating could cause water 
damage.
•  The removal of cabinet knockouts required for drain 
connections can be made much easier with the indoor 
coil assembly removed from the cabinet.
•  Install drain lines so they do not block service access 
to  front  of  unit. A  24”  clearance  is  required  for  lter, 
coil, or blower removal and service access.
•  Make  sure  unit  is  level  or  pitched  slightly  toward 
primary drain connection so that drain pan will empty 
completely without water standing in pan.
•  Install a 2” trap in the primary drain line as close to the 
unit as practical. Make sure that the top of the trap is 
below connection to the drain pan to allow complete 
drainage of pan.
•  Auxiliary drain (if used) should be run to a place 
where it would be noticeable if it becomes operational. 
Occupant  should  be  warned  that  a  problem  exists  if 
water  should  begin  running  from  the  auxiliary  drain 
line.
•  Test condensate drain pan and drain line after 
installation is complete. Pour several quarts of water 
into drain pan, enough to ll drain trap and line. Check 
to make sure drain pan is draining completely, no leaks 
are  found  in  drain  line  ttings,  and  water  is  draining 
from the termination of the primary drain line.
Unit
DrainConnection
Positive Liquid Seal Required
3.00" Min.
1.00" Min.
12.00"
Max.
Figure 1. Typical Condensate Drain Connection
A eld fabricated auxiliary drain pan, with a drain pipe to 
the outside of the building, is required in all installations 
over a nished living space or in any area that may be 
damaged by overow from the main drain pan. In some 
localities, local codes may require an auxiliary drain pan 
for any horizontal installation.
 CAUTION