Service Literature
Revised April 7, 2015
CBX32MV (HFC-410A) SERIES UNITS (iComfort
®
-enabled)
NOTICE
A thermostat is not included and must be ordered
separately.
A Lennox iComfort
®
thermostat must be used in
communicating applications.
In non-communicating applications, the Lennox
ComfortSense
®
7000 thermostat may be used, as well
as other non-communicating thermostats.
In all cases, setup is critical to ensure proper system
operation.
Field wiring for both communicating and non-
communicating applications is illustrated in diagrams,
which begin on page 24.
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take care
while handling this equipment and use protective cloth
ing.
TABLE OF CONTENTS
Specifications 2.................................
Model Identification 3............................
Blower Data 3..................................
Electric Heat Data 9.............................
Upflow/Downflow Unit Dimensions 13..............
Horizontal LH/RH Unit Dimensions 14..............
Installation Clearances 15.........................
General 15......................................
Installation Requirements 15......................
Brazing Connections 19...........................
Condensate Drain Requirements 22................
Inspecting and Replacing Filters 23.................
Sealing the Unit 23...............................
Field Control Wiring 24...........................
Air Handler Control Button, Display and Jumpers 31..
Configuring Unit 36...............................
Error Code Recall Mode 43........................
Indoor Blower Test 44............................
Checkout Procedures 44..........................
Operation 45....................................
Maintenance 45..................................
Cabinet Insulation 45.............................
Sequence of Operations 47.......................
Unit Components 60..............................
Electric Heat (ECB40) 66.........................
This indoor unit is designed for installation with optional
field-installed electric heat and a matched remote outdoor
unit that is charged with HFC-410A refrigerant. These units,
designed for indoor installation in multiple positions, are
completely assembled for upflow and horizontal right-hand
discharge before being shipped from the factory.
All CBX32MV air handlers are equipped with a
factory-installed, internally mounted check expansion
valve (CTXV), which is suitable for use in HFC-410A
applications.
This air handler is compatible with the ComfortSense® 7000
non-communicating thermostat and non- communicating
outdoor units. In addition, newer model units have the
enhanced capability of communicating with iComfort
®
thermostats and compatible outdoor units using the Lennox
RSBus protocols.
NOTE - For downflow or horizontal left-hand air discharge,
certain field modifications are required.
This document provides information only on the
CBX32MV-XXX-230-6-06 and later which features the new
iComfort-enabled hardware. Refer to Corp. 0206-L3 for
earlier model service related information.

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Lennox CBX32MV-024/030 and is the answer not in the manual?

Lennox CBX32MV-024/030 Specifications

General IconGeneral
BrandLennox
ModelCBX32MV-024/030
CategoryAir Conditioner
LanguageEnglish

Summary

Specifications

Electric Heat Data

Electric Heat Configurations and Ratings

Data tables for single and three-phase electric heat configurations and ratings.

Field Modifications for Left-Hand Discharge

Brazing Connections and Safety

Brazing Procedures and Precautions

Instructions and safety precautions for brazing refrigerant lines.

Field Control Wiring

Wiring Safety and Connection Guidelines

Safety warnings and instructions for field control wiring connections.

Jumper and Link Guide

Control Configuration and Error Management

Error Code Recall and Clearing

How to access, interpret, and clear error codes from the control.

Configuring Unit Size Codes

Configuring Electric Heat Sections

EVENHEAT Operation

Heat Pump and Electric Heat Integration

How EVENHEAT mode integrates heat pump and electric heat stages.

Heat Pump Operation

Cooling Operation

Error Code Recall Mode

Error Code Access and Clearing

Steps to enter and manage error codes on the air handler control.

Blower Test and System Checkout

Sequence of Operations

Electric Heat Wiring Diagrams (Single Phase)

ECB40 Electric Heat Models (2.5-5KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (6KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (8KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (9KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (12.5-15KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (20KW)

Wiring diagrams for ECB40 electric heat models.

Electric Heat Wiring Diagrams (Three Phase)

ECB40 Electric Heat Models (25KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (8-15KW)

Wiring diagrams for ECB40 electric heat models.

ECB40 Electric Heat Models (20-25KW)

Wiring diagrams for ECB40 electric heat models.

Blower Motor Troubleshooting

Troubleshooting (Regal-Beloit)

Specific troubleshooting steps for Regal-Beloit blower motors.

Indoor Blower Motor Troubleshooting (Emerson)

Optional Electric Heat (ECB40)