CLIMATIC™50 IOM Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
-
E
18
Loc Description Values Min Def lt Max
Loc1
It sets up the visualization of the great
field
1 = setpoint temperature (C°/F°)
2 = temperature (C°/F°)
3 = setpoint humidity (%Rh)
4 = humidity (%Rh) 1 2 4
Loc2
It sets up the visualization of the small
field
0 = No visualization
1 = setpoint temperature (C°/F°)
2 = temperature (C°/F°)
3 = setpoint humidity (%Rh)
4 = humidity (%Rh)
5 = Clock 0 5 5
Loc3 24 or 12h AM/PM
0 = 24H
1 = AM/PM 0 0 1
Loc4
Value in C° degrees to the setpoint of
temperature in the sleep mode Not used
-
5.0°C
0.0°C +5.0°C
Loc5 Ambient calibration probe temperature +/-10°C
-
9.5°C
0.0°c +9.5°C
Loc6 Ambient calibration probe humidity +/- 10% -10%
0% +10%
Loc7
It sets up the visualization to the first
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0 1 6
Loc8
It sets up the visualization to the second
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0
4 T. & Hu
6 T. only 6
Loc9
Address for the supervisor. For its
formulation it is necessary that finishes
is not associated they to some Access
Point. If finishes the parameter is
associated they is alone in reading. If
she wants herself to be removed from
the net they finishes look [16..199] 16 16 199
Loc10
It concurs to insert the password in
order to approach the parameters with
password
The value of the password is
defined from P11. And present a
value of default decided in factory
in order to concur the first access.
0 22 999
Loc11
Modification the password of access
(P10)
000-998 = new password
999 = it eliminates the password 0 999
Loc12
If set up to ON it eliminates finishes
them from the running net
disassociandolo from just the Access
Point
ON = Current value
OFF = Removal of the terminal on
the current network
Off On On
Loc13
It sets up the visualization to the third
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep
0
3 T. & Hu
0 T. only
6