Page 15
9 -  If the  common vertical  vent is  oset, the  maximum 
common vent capacity listed in the common venting 
tables should be reduced by 20%, the equivalent 
of two 90° elbows (0.80 x maximum common vent 
capacity). The horizontal length of the oset shall not 
exceed 1-1/2 feet (.46 m) for each inch (25 mm) of 
common vent diameter.
10 -  The vent pipe should be as short as possible with 
the least number of elbows and angles required to 
complete the job. Route the vent connector to the 
vent using the shortest possible route.
11 -  A vent connector shall be supported without any 
dips or sags and shall slope a minimum of 1/4 inch 
(6.4  mm)  per  linear  foot  (305  mm)  of  connector, 
back toward the appliance.
12 -  Vent  connectors  shall  be  rmly  attached  to  the 
furnace  ue  collar  by  self-drilling  screws  or  other 
approved means, except vent connectors of listed 
type B vent material which shall be assembled 
according to the manufacturer’s instructions. Joints 
between sections of single wall connector piping 
shall be fastened by screws or other approved 
means.
13 -  When the vent connector used for Category I 
appliances must be located in or pass through 
a crawlspace, attic or other areas which may 
be cold, that portion of the vent connector shall 
be constructed of listed double-wall type B vent 
material or material having equivalent insulation 
qualities.
14 -  All venting  pipe passing through oors, walls, and 
ceilings must be installed with the listed clearance 
to  combustible  materials  and  be  re  stopped 
according to local codes. In absence of local codes, 
refer to NFGC (Z223.1).
15 -  No portion of the venting system can extend into, 
or pass through any circulation air duct or plenum.
16 -  Vent connectors serving Category I appliances shall 
not be connected to any portion of mechanical draft 
systems operating under positive pressure such as 
Category III or IV venting systems.
17 -  If vent connectors are combined prior to entering 
the common vent, the maximum common vent 
capacity listed in the common venting tables must 
be reduced by 10%, the equivalent of one 90° elbow 
(0.90 x maximum common vent capacity).
18 -  The common vent diameter must always be at least 
as large as the largest vent connector diameter.
19 -  In no case, shall the vent connector be sized more 
than two consecutive table size diameters over the 
size of the draft hood outlet or ue collar outlet.
20 -  Do not install a manual damper, barometric draft 
regulator or ue restrictor between the furnace and 
the chimney.
21 -  When connecting this appliance to an existing 
dedicated or common venting system, you must 
inspect the venting system’s general condition 
and look for signs of corrosion. The existing vent 
pipe  size  must  conform  to  these  instructions  and 
the provided venting tables. If the existing venting 
system does not meet these requirements, it must 
be resized.