Page 26
10 -  Is  pressure  switch  closed?  Obstructed  ue  will 
cause unit to shut o at pressure switch. Check ue 
and outlet for blockages.
11 -  Are  ame rollout switches  tripped?  If ame  rollout 
switches are tripped, call the service technician for 
inspection.
Heating Sequence Of Operation (follow steps below)
1 -   When thermostat calls for heat, combustion air 
blower starts.
2 -  Combustion air pressure switch proves blower 
operation. Switch is factory-set and requires no 
adjustment.
3 -  After a 15-second prepurge, the hot surface ignitor 
energizes.
4 -  After a 20-second ignitor warm-up period, the gas 
valve solenoid opens. A 4-second trial for ignition 
period begins.
5 -  Gas is ignited, ame sensor proves the  ame, and 
the combustion process continues.
6 -  If  ame  is  not  detected  after  rst  ignition  trial,  the 
ignition control will repeat steps 3 and 4 four 
more times before locking out the gas valve 
(“WATCHGUARD” ame failure mode). The ignition 
control will then automatically repeat steps 1 through 
6 after 60 minutes.
7 -  To interrupt the 60-minute “WATCHGUARD” period, 
move thermostat from “Heat” to “OFF” then back to 
“Heat.” Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 8 
GAS METER CLOCKING CHART
Unit
Seconds for One Revolution
Natural LP/Propane
1 cu ft 
Dial
2 cu ft 
Dial
1 cu ft 
Dial
2 cu ft 
Dial
-040 90 180 n/a n/a
-060 60 120 150 300
-080 45 90 112 224
-100 36 72 n/a n/a
Natural-1000 btu/cu ft LP/Propane - 2500 btu/cu ft
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures a 
more accurate time.) Divide by two and compare to time in 
TABLE 8. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut o all other gas 
appliances  connected  to  meter.Supply Pressure Mea-
surement
On multiple unit installations, each unit should be checked 
separately, with and without units operating. Supply pres-
sure must fall within range listed in TABLE 9.
Check Manifold Pressure
1 -   Remove the threaded plug from the outlet side of 
the  gas  valve  and  install  a  eld-provided  barbed 
tting. Connect measuring device “+” connection to 
barbed tting to measure manifold pressure.
  Start unit and allow 5 minutes for unit to reach 
steady state.
2-   After allowing unit to stabilize for 5 minutes, record 
manifold pressure and compare to value given in  
TABLE 9. Make manifold adjustment if necessary
3 -   Shut unit o and remove manometer as soon as an 
accurate reading has been obtained.
4 -  Restart unit and check for any gas leaks. Seal any 
leaks if found.
 IMPORTANT
For  safety,  connect  a  shut-o  valve  between  the 
manometer  and  the  gas  tap  to  permit  shut  o  of  gas 
pressure to the manometer.
TABLE 9 
Supply Line and Manifold Pressure (inches w.c.)
Altitude 
ft
Unit
Natuarl LP/Propane
Manifold Supply Manifold Supply
0-4500 ft
-040 1.6-2.2
4.5-10.5
N/A N/A
-060
3.0-3.8
3.4-3.8
11.0-
13.0
-080
-100 N/A N/A
4501-
7500 ft
-040 1.4-2.0 N/A N/A
-060
2.5-3.3
2.5-3.3
11.0-
13.0
-080 N/A N/A
-100 N/A N/A
Proper Combustion & LP/Propane Conversion Kis
Furnace should operate minimum 15 minutes with correct 
manifold pressure and gas ow rate before checking com-
bustion. Take  combustion sample beyond  the ue outlet 
and compare to the table below.
TABLE 10 
Unit CO2% Nat CO2% LP
LP 
Conversion 
Kit
-040
6.5 - 7.5
N/A N/A
-060 7.5 - 9.0 20P40
-080 7.5 - 9.0 20P41
-100 N/A N/A
High Altitude
Units may be installed at altitudes up to 7,500 ft. above 
sea level. See Table 9 for de-rate manifold values. Units 
installed at altitude of 4501 - 7,500 feet require a pressure 
switch change which can be ordered separately. Table 11 
lists pressure switch requirements at high altitude. The 
combustion air pressure switch is factory-set and requires 
no adjustment.