Page 51
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow 
the  below  procedures  and  refer  to  gure  1  when  disas-
sembling unit. Use papers or protective covering in front of 
furnace while removing heat exchanger assembly.
1 -   Turn o electrical and gas supplies to the furnace.
2 -   Remove the furnace access panels.
3 -   Disconnect the wires from the gas valve.
4 -   Remove  gas  supply  line  connected  to  gas  valve. 
Remove  the  burner  box  cover  (if  equipped)  and 
remove gas valve/manifold assembly.
5 -   Remove  sensor  wire  from  sensor.  Disconnect 
2-pinplug from the ignitor.
6 -   Disconnect wires from ame roll-out switches.
7 -   Loosen  clamps  at  vent  elbow.  Disconnect 
condensate  drain  tubing  from  ue  collar.  and 
remove the vent elbow.
8 -   Loosen  clamps  and  remove  combustion air intake 
exible connector if equipped.
9 -   Remove  four  burner  box  screws  at  the  vestibule 
panel  and  remove  burner  box.  Set  burner  box 
assembly aside.
NOTE - If necessary, clean burners at this time. 
Follow  procedures  outlined  in  Burner  Cleaning 
section.
10 -  Mark  and  disconnect  all  combustion  air  pressure 
tubing from cold end header collector box.
11 -  Mark  and  remove  wires  from  pressure  switch 
assembly.  Remove  pressure  switch  assembly. 
Keep tubing   ttached to pressure switch assembly.
12 - 12  -  Disconnect  the  plug  from  the  combustion  air 
inducer. Remove two screws which secure combustion 
air  inducer  to  collector  box.  Remove  combustion  air 
inducer  assembly.  Remove  ground  wire  from  vest 
panel.
13 -  Remove electrical junction box from the side of the 
furnace.
14 -  Disconnect  condensate line from cold  end  header 
box. Remove cold end header box.
15 -  Loosen clamps on exhaust and air intake pipe seal 
plate. Slide exhaust and intake pipes up and out to 
clear blower deck. Remove exhaust and air intake 
pipe seal plate.
16 -  Mark  and  disconnect  any  remaining  wiring  to 
heating  compartment  components.  Disengage 
strain  relief  bushing  and  pull  wiring  and  bushing 
through the hole in the blower deck.
17 -  Remove the primary limit from the vestibule panel.
18 -  Remove  two  screws  from  the  front  cabinet  ange 
at the blower deck. Spread cabinet sides slightly to 
allow clearance for removal of heat exchanger.
19 -  Remove screws along vestibule sides which secure 
vestibule  panel  and  heat  exchanger  assembly  to 
cabinet. Remove two screws from blower rail which 
secure  top  heat  exchanger  ange.  Remove  heat 
exchanger from furnace cabinet.
20 -  Back  wash  heat  exchanger  with  soapy  water 
solution or steam. If steam is used it must be below 
275°F (135°C) .
21 -  Thoroughly  rinse  and  drain  the  heat  exchanger. 
Soap solutions can be corrosive. Take care to rinse 
entire assembly.
22 -  Reinstall heat exchanger into cabinet making sure 
that the clamshells of the heat exchanger assembly 
are  engaged  properly  into  the  support  bracket  on 
the blower deck. Remove the indoor blower to view 
this area through the blower opening.
23 -  Re-secure the supporting screws along the vestibule 
sides and top to the cabinet.
24 -  Reinstall  cabinet  screws on  front ange  at  blower 
deck.
25 -  Reinstall the primary limit on the vestibule panel.
26 -  Route  heating  component  wiring  through  hole  in 
blower deck and reinsert strain relief bushing.
27 -  Reinstall electrical junction box.
28 -  Reinstall  exhaust  and  air  intake  pipe  seal  plate. 
Reinstall exhaust  and air  intake  pipes and  tighten 
clamps on pipe seal plate.
29 -  Reinstall the cold end header box.
30 -  Reinstall the combustion air inducer. Reconnect the 
combustion air inducer to the wire harness.
31 -  Reinstall pressure switch assembly and reconnect 
pressure switch wiring.
32 -  Carefully  connect  combustion  air  pressure  switch 
tubing  from  pressure  switches  to  proper  ports  on 
cold end header collector box.
33 -  Reinstall condensate trap.
34 -  Secure  burner  box  assembly  to  vestibule  panel 
using four existing screws. Make sure burners line 
up in enter of burner ports.
35 -  Reconnect exhaust piping and exhaust drain tubing.
36 -  Reconnect ame roll-out switch wires.
37 -  Reconnect  sensor  wire  and  reconnect  2-pin  plug 
from ignitor.
38 -  Reinstall gas valve manifold assembly. Reconnect 
gas supply line to gas valve.
39 - Reinstall burner box cover if equipped.
40 - Reconnect plug to gas valve.
41 - Replace the blower compartment access panel.
42 -  Follow  lighting  instructions  on  unit  nameplate  to 
light  and operate  furnace  for 5  minutes  to  ensure 
the furnace is operating properly.
43 -  Check all piping connections, factory and eld, for 
gas  leaks.  Use  a  leak  detecting  solution  or  other 
preferred means.
44 -  Replace access panel.
 CAUTION
Some soaps used for leak detection are corrosive 
to certain metals. Carefully rinse piping thoroughly 
after leak test has been completed. Do not use 
matches, candles, ame or other sources of ignition 
to check for gas leaks.