5 - Remove sensor wire from sensor. Disconnect 2‐pin
plug from the ignitor.
6 - Disconnect wires from flame roll-out switches.
7 - Disconnect combustion air intake pipe. It may be nec
essary to cut the existing pipe to remove burner box
assembly.
8 - Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly
aside.
NOTE - If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
9 - Loosen the clamps to the flexible exhaust coupling.
10 - Disconnect condensate drain line from the cold end
header box.
11 - Disconnect condensate drain tubing from flue collar.
Remove screws that secures the flue collar into place.
Remove flue collar. It may be necessary to cut the exit
ing exhaust pipe for removal of the fitting.
12 - Mark and disconnect all combustion air pressure tub
ing from cold end header collector box.
13 - Mark and remove wires from pressure switch assemb
ly. Remove the assembly. Keep tubing attached to
pressure switches.
14 - Disconnect the plug from the combustion air inducer.
Remove two screws which secure combustion air in
ducer to collector box. Remove combustion air induc
er assembly. Remove ground wire from vest panel.
15 - Disconnect the condensate drain line.
16 - Remove cold end header box.
17 - Remove electrical junction box from the side of the fur
nace.
18 - Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole
in the blower deck.
19 - Remove the primary limit from the vestibule panel.
20 - Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger.
21 - Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as
sembly to cabinet. Remove two screws from blower
rail which secure bottom heat exchanger flange. Re
move heat exchanger from furnace cabinet.
22 - Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
23 - Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire
assembly.
24 - Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly is en
gaged properly into the support bracket on the blower
deck. Remove the indoor blower to view this area
through the blower opening.
25 - Re‐secure the supporting screws along the vestibule
sides and bottom to the cabinet.
26 - Reinstall cabinet screws on front flange at blower
deck.
27 - Reinstall the primary limit on the vestibule panel.
28 - Route heating component wiring through hole in blow
er deck and reinsert strain relief bushing.
29 - Reinstall electrical junction box.
30 - Reinstall the cold end header box.
31 - Reinstall the combustion air inducer. Reconnect the
plug to the wire harness.
32 - Reinstall pressure switches and reconnect pressure
switch wiring.
33 - Carefully connect combustion air pressure switch tub
ing from pressure switches to proper ports on cold end
header collector box.
34 - Reconnect condensate drain line to the cold end
header box.
35 - Use securing screws to reinstall flue collar to the top
cap on the furnace. Reconnect exhaust piping and ex
haust drain tubing.
36 - Replace flexible exhaust adapter on combustion air in
ducer and flue collar. Secure using two existing hose
clamps.
37 - Reinstall burner box assembly in vestibule area. Se
cure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports
38 - Reconnect flame roll-out switch wires.
39 - Reconnect sensor wire and reconnect 2-pin plug from
ignitor.
40 - Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve.
41 - Reconnect the combustion air intake pipe.
42 - Reinstall burner box cover.
43 - Reconnect wires to gas valve.
44 - Replace the blower compartment access panel.
45 - Reconnect gas supply piping. Turn on power and gas
supply to unit.
46- Follow lighting instructions on unit nameplate to light
and operate furnace for 5 minutes to ensure the fur
nace is operating properly.
47- Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
48- Replace heating compartment access panel.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly af
ter leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.