Page 32
Ignition Control 107045-XX Diagnostic Modes
Code
Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E124 Active  communicating  thermostat  signal 
missing for more than 3 minutes.
Equipment  lost  communication  with  the  thermostat.  Check 
four wiring connections,  ohm  wires  and cycle power at  the 
thermostat. Alert  stops  all  services  and  waits  for  heartbeat 
message from thermostat (subnet controller). Cleared  after 
valid thermostat (subnet controller) message is received.
E125 Control  failed  self-check,  internal  error, 
failed hardware. Will restart if error recov-
ers. Integrated control not communicating. 
Covers hardware errors (ame sense cir-
cuit faults, pin shorts, etc.).
Hardware  problem  on  the  control.  Cycle  power  on  control. 
Replace if problem prevents service and is persistent. Criti-
cal alert. Cleared 300 seconds after fault recovered.
E131 Corrupted control parameters (Verify con-
guration of system). Communicating only.
Recongure the system. Replace control if heating or cool-
ing  is  not  available.  Only  applicable  in  the  communicating 
mode, not in startup. Exit from Commissioning and Execute 
‘Set Factory Default mode Control will still operate on default 
parameter settings
E150 A2L Regerant leak alarm
E151 A2L Sensor  fault  (sensor  problem)  (com-
munication mode only)
E180 Outdoor  air  temperature  sensor  failure. 
Only shown if shorted or out-ofrange.
Compare  outdoor  sensor  resistance  to  temperature/  resis-
tance charts in unit installation instructions. Replace sensor 
pack if necessary. At beginning of (any) conguration, furnace 
or  air  handler  control  will  sense  outdoor  air  and  discharge 
air  temperature  sensor(s).  If  detected  (reading  in  range), 
appropriate  feature  will  be  set  as  ‘installed’  and  that  could 
be seen in ‘About’ screen. In normal operation after control 
recognizes sensors,  alarm  will  be  sent if  valid  temperature 
reading is lost. To get rid of setting and alarm, redo congu-
ration and make sure that temperature sensor is marked as 
‘not installed’ in Indoor Unit ‘About’ screen. When Indoor unit 
control  is  replaced,  thermostat  will  ‘tell’ new  control  if  tem-
perature sensor is in system or not. Clears 30 seconds after 
fault recovered.
E200 Hard lockout - Rollout circuit open or pre-
viously open.
Correct cause of rollout trip, or replace ame rollout switch. 
Test furnace operation. Cleared after fault recovered.
E201 Indoor blower communication failure - Un-
able to communicate with blower motor.
Indoor  blower  communication  failure  (including  power  out-
age). Lost communication with indoor blower motor. Possible 
causes: motor not  powered,  loose  wiring.  Problem may be 
on control or motor side. Cleared after fault recovered.
E202 Indoor  blower  motor  mis-match  -  Indoor 
motor horsepower does not match unit ca-
pacity.
Incorrect appliance capacity code selected. Check for proper 
conguring under: Unit Size Codes for Furnace/Air Handler 
on conguration guide or in installation instructions. Cleared 
after  the  correct  match  is  detected  following  a  reset.  (Re-
move thermostat from system while applying power and re-
programming.)
E203 Appliance  capacity  /  size  is  NOT  pro-
grammed. Invalid unit codes refer to con-
guration ow chart.
No appliance capacity code selected. Check for proper con-
guring under: Unit Size Codes for Furnace on conguration 
guide or in installation instructions. Critical Alert. Cleared af-
ter valid unit code is read following a reset. (Remove thermo-
stat from system while applying power and reprogramming.)
E204 Gas valve mis-wired. Check gas valve operation and wiring. Clears when repaired.
E205 Gas valve control relay contact shorted. Check wiring  on  control  and  gas valve.  If  wiring is  correct, 
replace control.