Page 45
NOTE - In heat pump mode blower operation defaults to 
option c.
TABLE 7 
Cooling Mode Blower Speed Ramping
Ramping Switch 9 Switch 10
A (Factory) O O
B O On
C On O
D On On
Ramping Option A (Factory Selection)
•   Motor runs at 50% for 30 seconds.
•   Motor  then  runs  at  82%  for  approximately  7-1/2 
minutes.
•   If demand has not been satised after 7-1/2 min-
utes, motor runs at 100% until demand is satised.
•   Once  demand  is  met,  motor  runs  at  50%  for  30 
seconds then ramps down to stop.
OFF
1/2 MIN
50% CFM
COMPRESSOR DEMAND
7 1/2 MIN
82% CFM
100% 
CFM
1/2 MIN
50% CFM
 
Ramping Option B
•   Motor runs at 82% for approximately 7-1/2 minutes. 
If  demand  has  not  been  satised  after  7-1/2  min-
utes, motor runs at 100% until demand is satised. 
•   Once demand is met, motor ramps down to stop.
OFF
OFF
82%CFM
100% CFM
COMPRESSOR DEMAND
7 1/2 MIN
 
Ramping Option C
•    Motor runs at 100% until demand is satised.
•   Once  demand  is  met,  motor  runs  at  100%  for  45 
seconds then ramps down to stop.
OFF
100% CFM
100% CFM
45 SEC.
COMPRESSOR
DEMAND
 
Ramping Option D
•  Motor runs at 100% until demand is satised.
•  Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COMPRESSOR
 DEMAND
 
Switches 11, 12 and 13 -- Heating Mode Blower Speed  
The  switches  are  factory  set  to  the  OFF  position  which 
provides factory default heat speed. Refer to TABLE 8 for 
switches 11,  12  and 13  that  provided the  corresponding 
increases or decrease to both high and low heat demand. 
TABLE 8 
Heating Mode Blower Speeds
Heat Speed Switch 11 Switch 12 Switch 13
Increase 24% On On On
Increase 18% On On O
Increase 12% On O On
Increase 6% On  O O
Factory 
Default
O O O
Decrease 6% O O On
Decrease 
12%
O On O
Decrease 
18%
O On On
Switches 14 and 15 -- Continuous Blower Speed --
TABLE 9 provides continuous blower speed adjustments 
that will result from dierent switch settings.
TABLE 9 
Continuous Blower Speed
Continuous Blower Speed Switch 14 Switch 15
28% of High Cool Speed O On
38% of High Cool Speed
(Factory Setting)
O O
Switch 16 - Not Used