Page 51
Troubleshooting Motor Windings
Ensure that motor windings are not damaged by perform-
ing the following tests:
NOTE - If your ohm meter is not an auto-ranging type, set 
it to the highest ohm scale (100k ohms or greater) before 
performing tests.
TABLE 13 
Ohm Meter Range
Scale Measurement Range
in words ohms
2M two megohm -- two 
million ohms
0-2,000,000
200K two hundred kilohm -- 
two hundred thousand 
ohms
0-200,000
20K twenty kilohm -- twenty 
thousand ohms
0-20,000
2K two kilohm -- two thou-
sand ohms
0-2,000
200 two hundred ohm 0-200
FIGURE 12 
TEST A
Measure the resistance between each of the three motor 
leads (3-pin plug) and the unpainted part of the end shield.
If the winding resistance to ground is <100k ohms, replace 
the motor and control module. If the resistance to ground 
is >100k, the motor windings are ne. Proceed to Test B.
FIGURE 13 
TEST B
Use an ohmmeter to measure the motor phase-to-phase 
resistance by checking these combinations of the the 3-pin 
motor plug. For the purpose of this test, start at either end 
of the connector as lead 1.
1 -   The  lead-to-lead  resistance  across  any  two  leads 
should be less than 20 ohms.
2 -   Each lead-to-lead resistance should be the same. If 
the measured resistance is greater than 20 ohms, 
replace the motor and control module.
FIGURE 14 
Models with the Lennox Blower Drive
Removed  the  three  blower  leads  from  the  blower  drive. 
see TEST A. If ohms to ground shows resistance replace 
motor. If the circuit is open move to test B and table below 
for acceptable resistance. If ohm reading is met motor has 
passed.  If  the  motor  passes  both  test A  and  B  and  the 
shaft spins freely by hand, replace the blower drive.
Motor HP Ohm Reading
1/2
7.6 + .76
3/4
6.3 + .63
1
4.7 + .47