Page 55
7. Combustion Air Inducer (B6) and
Cold End Header Box
All EL297UHV(X) units use a two-stage combustion air in-
ducer to move air through the burners and heat exchanger 
during heating operation. The blower uses a 120VAC mo-
tor. The motor operates during all heating operation and 
is controlled by integrated control A92. The  inducer  also 
operates for 15 seconds before burner ignition (prepurge) 
and for 5 seconds after the gas valve closes (postpurge). 
The inducer operates on low speed during rst stage heat, 
then switches to high speed for second stage heat.
NOTE - Each furnace model uses a unique CAI. Refer to 
Lennox Repair Parts listing for correct inducer for replace-
ment.
The  combustion  air  inducer  is  installed  on  the  cold  end 
header  box.  The  cold  end  header  box  is  a  single  piece 
made  of  hard  plastic.  The  box  has  an  internal  channel 
where the combustion air inducer creates negative pres-
sure at unit start up. The channel contains an orice used 
to regulate ow created by the combustion air inducer.
The box has pressure taps for the combustion air induc-
er pressure switch hoses. The pressure switch measures 
the pressure dierential across the combustion air inducer 
orice or dierence in the channel and the box. If replace-
ment is necessary the gaskets used to seal the box to 
the vestibule panel and the combustion air inducer to 
the box, must also be replaced.
A proving switch connected to the combustion air inducer 
orice plate is used to prove inducer operation. The com-
bustion air inducer orice will be dierent for each model. 
See TABLE 15 for orice sizes. The pressure switch mea-
sures the pressure dierential across the combustion air 
inducer  orice.  When  the  proving  switch  opens,  the  fur-
nace  control  (A92)  immediately  closes  the  gas  valve  to 
prevent burner operation.
TABLE 15 
EL297UHV Unit C.A.I. Orice Size
-045 0.650
-070 0.810
-090 0.920
-110 1.070
-135 1.300
8. Combustion Air Inducer
Pressure Switch (S18)
EL297UHV(X) series units are equipped with a dual com-
bustion  air  pressure  switch  (rst  and  second  stage)  lo-
cated on the combustion air inducer orice bracket. See 
FIGURE 17. The switch is connected to the combustion 
air inducer housing by means of a exible silicone hose. 
It monitors negative air pressure in the combustion air in-
ducer housing.
The  switches  are  a  single-pole  single-throw  pressure 
switch electrically connected to the integrated control. The 
purpose of the switch is to prevent burner operation if the 
combustion air inducer is not operating or  if  the ue be-
comes obstructed.
On heat demand (rst or second stage) the switch senses 
that  the  combustion  air  inducer  is  operating.  It  closes  a 
circuit to the integrated control when pressure inside the 
combustion air  inducer  decreases  to a certain  set  point. 
Set  points  vary  depending  on  unit  size.  See  TABLE  16 
0    -  4500’  The  pressure  sensed  by  the  switch  is  nega-
tive relative to atmospheric pressure. If the ue becomes 
obstructed during operation, the switch senses a loss of 
negative pressure becomes more equal with atmospheric 
pressure) and opens the circuit to the furnace control and 
gas valve. A bleed port on the switch allows relatively dry 
air in the vestibule to purge switch tubing, to prevent con-
densate build up.
NOTE - The switch is factory  set and is not eld adjust-
able. It  is  a  safety  shut-down  control  in the  furnace  and 
must not be by-passed for any reason. If switch is closed 
or bypassed, the control will not initiate ignition at start up.
COMBUSTION AIR PRESSURE SWITCH
High Fire Switch
Low Fire Switch
Positive Port
Negative Port
FIGURE 17 
TABLE 16 0  - 4500’
Unit Set Point High Heat  Set Point Low Heat
-045 0.80 0.50
-070 0.95 0.55
-090 0.90 0.50
-110 1.00 0.55
-135 0.85 0.45
TABLE 17  4501 - 7500’
Unit Set Point High Heat  Set Point Low Heat
-045 0.74 0.41
-070 0.85 0.50
-090 0.75 0.45
-110 0.95 0.55
-135 0.80 0.40
TABLE 18  7500 - 10,000’
Unit Set Point High Heat  Set Point Low Heat
-045 0.70 0.40
-070 0.75 0.45
-090 0.70 0.40
-110 0.90 0.50
-135 0.75 0.35