Page 80
IV-HEATING SYSTEM SERVICE CHECKS
A-CSA Certication
All  units  are  CSA  design  certied  without  modications. 
Refer to the EL297UHV(X) Installation Instruction.
B-Gas Piping
 CAUTION
If a exible gas connector is required or allowed by 
the authority that has jurisdiction, black iron pipe 
shall be installed at the gas valve and extend outside 
the furnace cabinet.
 WARNING
Do not over torque (800 in-lbs) or under torque (350 
in-lbs) when attaching the gas piping to the gas 
valve.
Gas  supply  piping  should  not  allow  more  than  0.5”W.C. 
drop in pressure between gas meter and unit. Supply gas 
pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be 
resistant to action of liqueed petroleum gases.
C-Testing Gas Piping
 IMPORTANT
In case emergency shutdown is required, turn o the 
main shut-o valve and disconnect the main power 
to unit. These controls should be properly labeled 
by the installer.
When pressure testing gas lines, the  gas valve must be 
disconnected and isolated. Gas valves can be damaged if 
subjected to more than 0.5 psig (14” W.C.). See FIGURE 
53. If the pressure is greater than 0.5psig (14”W.C.), use 
the manual shut-o  valve before pressure testing to iso-
late furnace from gas supply.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8” N.P. T. PLUGGED TA P
FIGURE 53 
When  checking  piping  connections  for  gas  leaks,  use 
preferred  means.  Kitchen  detergents  can  cause  harmful 
corrosion on various metals used in gas piping. Use of a 
specialty Gas Leak Detector is strongly recommended. It 
is available through Lennox under part number 31B2001. 
See Corp. 8411-L10, for further details.
Do  not  use  matches,  candles,  ame  or  any  other 
source of ignition to check for gas leaks.
D-Testing Gas Supply Pressure
An inlet post located on the gas valve provides access to 
the supply pressure. See FIGURE 52. Back out the 3/32 
hex screw  one  turn,  connect a piece  of  5/16  tubing and 
connect to a manometer to measure supply pressure. See 
TABLE 28 for supply line pressure.
E-Check Manifold Pressure
A  manifold  pressure  post  located  on  the  gas  valve  pro-
vides access to the manifold pressure. See FIGURE 52. 
Back  out  the  3/32  hex  screw  one  turn,  connect  a  piece 
of 5/16  tubing and  connect  to  a  manometer  to  measure 
manifold pressure.
To  correctly  measure  manifold  pressure,  the  dierential 
pressure between the positive gas manifold and the neg-
ative burner box must be considered.
 IMPORTANT
For  safety,  connect  a  shut-o  valve  between  the 
manometer and the gas tap to permit shut o of gas 
pressure to the manometer.
The gas valve is factory set and should not require adjust-
ment. All gas valves are factory regulated.
1 -   Connect the test gauge positive side “+“ to manifold 
pressure tap on gas valve as noted above.
2 -   Tee  into  the  gas  valve  regulator  vent  hose  and 
connect to test gauge negative “-”.
3 -   Ignite unit  on  low re  and  let run  for  5 minutes  to 
allow for steady state conditions.
4 -   After allowing unit to stabilize for 5 minutes, record 
manifold  pressure  and  compare  to  value  given  in 
TABLE 28.
5 -   If necessary, make adjustments. FIGURE 52 shows 
location of high re and low re adjustment screws.
6 -   Repeat steps 3, 4 and 5 on high re. See values in 
TABLE 28.
7 -   Shut unit o and remove manometer as soon as an 
accurate reading has been obtained.
8 -   Start  unit  and  perform  leak  check.  Seal  leaks  if 
found.
F- Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures 
a more accurate time.) Divide by two and compare to time 
in TABLE 26. If manifold pressure matches TABLE 26 and 
rate  is  incorrect,  check  gas  orices  for  proper  size  and 
restriction.