Page 82
I- Proper Ground and Voltage
A  poorly  grounded  furnace  can  contribute  to  premature 
ignitor  failure.  Use  the  following  procedure  to  check  for 
ground and voltage to the integrated control.
1 -   Measure  the  AC  voltage  between  Line  Neutral 
(spade  terminals)  and  “C”  terminal  (low  voltage 
terminal  block)  on  the  integrated  control.  See 
FIGURE 54. A wide variation in the voltage between 
Line Neutral and “C” as a function of load indicates 
a poor or  partial ground. Compare the readings to 
TABLE  30.  If  the  readings  exceed  the  maximum 
shown in table 1, make repairs before operating the 
furnace.
NOTE - FIGURE 54 is a typical ignition illustration. 
Use as reference.
2 -   In addition, measure the AC voltage from Line Hot 
to Line Neutral (spade terminals) on the integrated 
control. See FIGURE 54. This voltage should be in 
the range of 97 to 132 Vac.
TABLE 30 
Furnace Status
Measurement VAC
Expected Maximum
Power On Furnace Idle 0.3 2
CAI / Ignitor Energized 0.75 5
Indoor Blower Energized Less than 2 10
CHECK VOLTAGE BETWEEN LINE NEUTRAL
AND LOW VOLTAGE “C” TERMINAL
CHECK VOLTAGE BETWEEN LINE HOT
AND LINE NEUTRAL
W1 W2 G
Y2
Y1
CC
RDHL ODS
W1 W2 G
Y2
Y1
CC
RDHL ODS
FIGURE 54