Page 74
2 -   On  eld  supplied  terminations  for  side  wall  exit, 
exhaust piping may extend a maximum of 12 inches 
(305MM) for 2” PVC and 20 inches (508MM) for 3” 
(76MM) PVC beyond the outside wall.
3 -   If  exhaust  piping  must  be  run  up  a  side  wall 
to  position  above  snow  accumulation  or  other 
obstructions,  piping  must  be  supported  every  24 
inches (610MM). When exhaust piping must be run 
up  an  outside  wall,  any  reduction  in  exhaust  pipe 
size must be done after the nal elbow.
4 -    Distance  between  exhaust  pipe  terminations  on 
multiple furnaces must meet local codes.
NON-DIRECT VENT ROOF TERMINATION KIT
UNCONDITIONED
ATTIC SPACE
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
12” (305mm)
ABOVE AVE.
SNOW
TION
FIGURE 41 
NOTE - Do 
tical discharge through an existing unused chimney or stack is required, insert piping
inside 
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
       NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
FIGURE 42 
Condensate Piping
This  unit  is  designed  for  either  right-  or  left-side  exit  of 
condensate  piping  in  upow  applications.  In  horizontal 
applications, the condensate trap must extend below the 
unit. An 8” service clearance is required for the conden-
sate trap. Refer to FIGURE 43 for condensate trap loca-
tions.  FIGURE 51 shows trap assembly
NOTE - If necessary the condensate trap may be installed 
up to 5’ away from the furnace. Use PVC pipe to connect 
trap  to  furnace  condensate  outlet.  Piping  from  furnace 
must slope down a minimum of 1/4” per ft. toward trap.
1 -   Determine  which  side  condensate  piping  will  exit 
the unit, location of trap, eld-provided ttings and 
length  of  PVC  pipe  required  to  reach  available 
drain.
2 -   Use  a  large  at  head  screw  driver  or  a  1/2”  drive 
socket extension and remove plug (Figure 45) from 
the cold end header box at the appropriate location 
on  the  side  of  the  unit.  Install  provided  3/4  NPT 
street  elbow  tting  into  cold  end  header  box.  Use 
Teon tape or appropriate pipe dope.
NOTE - Cold end header box drain plugs are factory 
installed.  Check  the  unused  plug  for  tightness  to 
prevent leakage.
3 -   Install  the  cap  over  the  clean  out  opening  at  the 
base of the trap. Secure with clamp. See FIGURE 
51.
4 -   Install  drain  trap  using  appropriate  PVC  ttings, 
glue  all  joints.  Glue  the  provided  drain  trap  as 
shown  in  FIGURE  55.  Route  the  condensate  line 
to an open drain. Condensate line must maintain a 
1/4” downward slope from the furnace to the drain.
CONDENSATE TRAP AND PLUG  LOCATIONS
(Unit shown in upflow position)
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
Trap
(same on
right side)
Plug
(same on left side)
1-1/2 in.
Rubber
Grommet
FIGURE 43 
5 -   FIGURE 46 and FIGURE 48 show the furnace and 
evaporator coil using a separate drain. If necessary 
the condensate line from the furnace and evaporator 
coil can drain together. See FIGURE 47, FIGURE 
49 and FIGURE 50 .
Upow  furnace  (FIGURE  49)  -  In  upow  furnace 
applications  the  eld  provided  vent  must  be  a 
minimum  1”  to  a  maximum  2”  length  above  the 
condensate  drain  outlet  connection.  Any  length 
above  2”  may  result  in  a  ooded  heat  exchanger 
if the combined primary drain line were to become 
restricted.