Furnace with Evaporator
Coil Using a Common Drain
(1” min.to2 Max.above
condensatedrain connection)
Condensate
Drain
Connection
Evaporator drain
line required
(Trap at coil is optional)
FIGURE 49
Furnace with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
(4” min.to5 Max.above
condensatedrain
connection)
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain
Pan
Piping from furnace and evaporator coil must slope
down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
FIGURE 50