IOM / ROOF-TOP FLEXY™ Series - Page 75
Refrigeration system faults
Faulty condensor temperature sensor
Faulty pressure transmitter sensor, refrigeration system
Faulty refrigeration system, frost temperature sensor
High pressure switch safety or compressor electrical safety
The compressor contactor is not connected although the CLIMATIC requests it.
- The high pressure pressostat is open.
- The internal protection of the compressor motor is open.
The high pressure pressostat and the compressor motor thermal protection act directly
on the compressor contactor. This information is transmitted to the CLIMATIC via
an auxiliary contact of the contactor.
If the CLIMATIC gives the order to operate to the compressor and if the auxiliary
contact is still open 5 seconds later, the fan safety system is activated and stops the
compressor.The safety system automatically cuts out after 4 minutes.
It is also automatically locked out after 3 failures within a day. In this case, manual
resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value
does not exceed 3 failures.
Faulty low pressure compressor
If the low pressure pressostat is open and the compressor has been operating for
more than 2 minutes, the low pressure safety system is activated and stops the
compressor. This safety system is not taken into account during the defrost cycle for
the heat pump units.
The compressor is engaged when the pressostat contact closes.
It is also automatically locked out after 3 failures within a day. In this case, manual
resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value
does not exceed 3 failures.
SAFETY AND ERROR CODESSAFETY AND ERROR CODES
SAFETY AND ERROR CODESSAFETY AND ERROR CODES
SAFETY AND ERROR CODES
111
121
131
141
112
122
132
142
113
123
133
143
115
125
135
145
117
127
137
147