6.
Inspect
drain
holes
in
coil
compartment
base
and
clean
If
necessary.
NOT£
If insufficient
cooling
occurs,
the
unit
should
be
gauged
and
refrigerant
charge
Should
b.e
checked.
Outdoor Coli
Clean
and
inspect
outdoor
coil
(may
be
flushed
with
a
water
hose).
Ensure
power
is
off
before
cleaning.
NOTE
- It
may
be
necessary
to
flush
the
outdoor
coil
more
frequently
if
it
is
exposed
to
substances
which
are
corrosive
or
which
block airflow
across
the
coli
(e.g.,
pet
urine,
cottonwood
seeds,
fertilizers,
fluids
that
may
contain
high
levels
of
corrosive
chemicals
such
as
salts)
Sea
Coast
-
Moist
air
in
ocean
locations
can
carry
salt,
which
is
corrosive
to
most
metal.
Units
that
are
located
near
the
ocean
require
frequent
inspections
and
maintenance.
These
inspections
will
determine
the
necessary
need
to
wash
the
unit
induding
the
outdoor
coil.
Consult
your
Installing contractor for proper
intervals/procedures
for
your geographic
area
or
service
contract.
Indoor Unit
1.
Clean
or
change
filters.
2.
Lennox
blower
motors
are
prelUbricated
and
permanently
sealed.
No
more
lubrication
Is
needed.
3.
Adjust
blower
speed
for
cooling.
Measure
the
pressure
drop
over
the
roil
to
determine
the
correct
blower
CFM.
Refer
to
the
unit
information
service
manual
fOr
pressure
drop
tables
and
procedure.
4.
Be/t
Drlv9
B/owers
-
ChecK
belt
for
wear
and
proper
tensIon.
5.
Check
all
wiring
for
loose
connections.
6.
Check
for
correct
voltage
at
unit.
(blower
operating)
7.
Check
amp
draw
on
blower
motor.
Motor Nameplate: Aclual: _
Indoor Coil
1.
Clean
coil
if
necessary.
2.
Check
connecting
lines,
Joints
and
coil
for
evidence
of
oil
leaks.
3.
Check
condensate
line
and
clean
if
necessary.
Job
Name
_
Job
no.
_
Date
Job
Location
_
Cily _
State
Installer _
City
_
State
Unit
Model
No.
SerIal
No.
_
Service
Technician
~
Nameplate
Voltage
Rated
Load
Ampacity
Compressor
_
Outdoor
Fan
Maximum
Fuse
or
Circuit Breaker
Electrical
Conneclions light? 0 Indoor
Filter
clean?
0
Supply
Voltage
(Unit
Off)
Indoor
Blower
RPM
S.P.
Drop
Over
Indoor
(Dry)
_
Outdoor
Call
Entering
Air
Temp.
Discharge
Pressure
__
Suction
Pressure
_
Refrigerant
Charge
Checked?
Re~~~_!~~_~~_~~!"es:_.:_.~!~.~
..
~.~:.:~~~.?.J:;:;!..
Service Valves: --
..
Fully
Opened?
0
_
....
-
..
_-------~-_
Voltage
With
Compressor
Operating
~.~~.~:~~
I~.~~~~~~.~?.g
..
_
9..~_~~?~.~.~~.~~~.~.?~~~?
_
__
Caps
light? 0 Thermostat
Calibrated?
0 Properly
Set?
0
_
_
_
_
_
_
_
_
o
_
_Q .
Level?
0
Page
29
1:lACll
SERIES