Page 52
TABLE 27
G61MPV−60D−135 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1470 695 1650 780 1845 870 2040 965 1585 750 1705 805 1905 900 2130 1005
NORM 1325 625 1495 705 1680 795 1865 880 1430 675 1545 730 1765 835 1975 930
N/A
N/A 1335 630 1505 710 1670 790 1275 600 1370 645 1565 740 1755 830
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1335 630 1510 710 1695 800 1870 885 1105 520 1180 555 1330 630 1500 710
NORM 1210 570 1370 645 1540 725 1710 810 990 465 1075 505 1210 570 1355 640
N/A N/A 1225 575 1375 650 1515 715 890 420 950 450 1085 515 1210 570
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm (220 L/s).
TABLE 28
G61MPV−60D−135 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air with optional RAB return air base
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1445 685 1635 770 1825 860 2025 955 1550 730 1660 785 1875 885 2105 995
NORM 1305 615 1475 695 1660 785 1840 870 1400 660 1510 715 1720 810 1920 905
N/A
N/A 1315 620 1480 700 1650 780 1250 590 1345 635 1530 725 1715 810
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1315 620 1490 705 1675 790 1855 875 1080 510 1155 545 1310 620 1478 695
NORM 1195 565 1365 645 1530 725 1695 800 985 465 1055 500 1190 560 1325 625
N/A N/A 1210 570 1360 640 1500 710 875 410 945 445 1060 500 1190 560
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm (220 L/s).