G61MPV / Page 8
EXHAUST PIPE VENTING TABLE (For altitudes of 0−10,000 ft)
1
Maximum Equivalent Vent Length − ft.
G61MPV
G61MPV
G61MPV
G61MPV
G61MPV
2
G61MPV
2
G61MPV
3
G61MPV
en
pe
Diameter
−36B−045
−36B−070 −36B−071 −36C−090
−60C−090
−60C−091 −60C−110 −60C−111 −60D−135
2 in. 59 59
4
59 26
4
26 not allowed not allowed not allowed
2−1/2 in. 65 65
4
65 42
4
42 32
4
32 not allowed
3 in. 77 78
4
78 72
4
72 72
4
72
4
61 (0−4500 ft.)
4
46 (4501 − 10,000 ft.)
4 in. 234 214 214 204 204 179 179 160
NOTE − Minimum Equivalent Vent Pipe length is 15 feet (4.6 m).
1
Maximum Equivalent Vent Length" permitted is defined as Total Length (linear feet) of vent pipe, plus equivalent length (ft.) of fittings, plus equivalent length (ft.) of termination".
2
110 and 111 models installed in up−flow or down−flow applications must have the supplied 90° street ell installed directly into the unit flue collar. The street ell must be included
in the elbow count.
3
135 models installed in up−flow or down−flow applications must have 3 in. to 2 in. reducing elbow (supplied) installed directly into the flue collar. Reducing ell must be included
in elbow count.
4
90 elbows must be limited to sweep type elbows.
VENTING NOTES One 90elbow is equivalent to 5 feet of straight vent pipe.
Two 45 elbows are equal to one 90 elbow.
One 45 elbow is equivalent to 2.5 feet of straight vent pipe.
Wall and roof termination (non−concentric) exhaust pipe must terminate with reducer to improve exhaust velocity away from intake piping.
045, 070 and 071 − 2, 2−1/2, 3 or 4 in. − terminate with 1−1/2 in. pipe
090 and 091 − 2, 2−1/2, 3 or 4 in. − terminate with 2 in. pipe
110 and 111 − 2−1/2, 3 or 4 in. − terminate with 2 in. pipe
135 − 3 or 4 in. − terminate with 2 in. pipe
TERMINATION KITS − EQUIVALENT VENT LENGTHS
Vent Pipe Equivalent Length − ft.
Heat
Vent
Pipe
Concentric
Kits
Close Couple
Kits
Wall Ring
Kit
Outdoor Exhaust
Accelerator
(Diameter X Length)
Size
Diameter
in.
2 in. 3 in. 2 in. 3 in. 2 in. 1−1/2 x 12 in. 2 x 12 in.
.
4
71M80
69M29
60L46
22G44
30G28 (WTK)
44J40
81J20 (WTK)
15F74 − − − − − −
2 12 not allowed 4
1
4 4 4 not allowed
2−1/2 15 not allowed 5
1
5 5 5 not allowed
−
3 21 not allowed 7
1
7 7 7 not allowed
4 42 not allowed 14
1
14 14 14 not allowed
2 12 not allowed 4
1
4 4 4 not allowed
−070
2−1/2
15 not allowed 5
1
5 5 5 not allowed
−071
3
24 not allowed 8
1
8 8 8 not allowed
4 42 not allowed 14
1
14 14 14 not allowed
2 3 3 not allowed 1
2
1 not allowed 1
−090
2−1/2
6 6 not allowed 2
2
2 not allowed 2
−091
3
6 6 not allowed 2
2
2 not allowed 2
4 12 12 not allowed 4
2
4 not allowed 4
2 3 3 not allowed 1
2
1 not allowed 1
−110
2−1/2
6 6 not allowed 2
3
2 not allowed 2
−111
3
6 6 not allowed 2
3
2 not allowed 2
4 12 12 not allowed 4
3
4 not allowed 4
3 not allowed 15 not allowed 6
3
6 not allowed 6
−
4 not allowed 25 not allowed 10
3
10 not allowed 10
1
Requires field provided 1−1/2 in. outdoor exhaust accelerator.
2
Requires field provided 2 in. outdoor exhaust accelerator.
3
For use only in non−direct vent applications, when snow riser is not required. Requires field provided 2 in. outdoor exhaust accelerator.
4
Outdoor exhause accelerator included in 71M80 kir; for use with −045−070−071 models.