EasyManua.ls Logo

Lennox G61MPV

Lennox G61MPV
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 101
B−SureLight
®
Board 100870
Two Stage Variable Speed Control Board 100870
UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Flash Code
LED X + Y
Possible Cause Corrective Action / Comments
1.1
Diagnostic lights fail to light up.
LED OFF
1.1.1
Main voltage 120V not supplied to unit.
ACTION 1 − Check 120V main voltage.
Determine cause of main power failure.
1.1.2
Miswiring of furnace or improper con-
nections.
ACTION 1 − Check for correct wiring of 120V to
power make up box and transformer.
ACTION 2 − Check 24V wiring to control board.
1.1.3
Circuit breaker tripped or fails to
close.
ACTION 1 − Replace circuit breaker if it is reset
but does not have continuity.
ACTION 2 − If circuit breaker still trips, check for
short.
1.1.4
Door interlock switch failure.
ACTION 1 − Check that door switch is activated
when door is closed.
ACTION 2 Check wire connections to switch, re-
place loose connectors.
ACTION 3 − Check continuity of switch in closed
position. Replace if defective.
1.1.5
Transformer Failure.
ACTION 1 − Check that transformer output is
24V. Replace if defective.
1.1.6
Failed control board.
ACTION 1 − If all the above items have been
checked, replace board.
1.2
Diagnostic light flashes the reverse
polarity code.
LED 5 + 4
1.2.1
120V main power polarity reversed.
ACTION 1 − Check the 120V has line and neutral
correctly input into control.
ACTION 2 − Reverse the line and neutral at the
120V field connection.
1.3
Diagnostic light flash the improper
main ground.
LED 5 + 3
1.3.1
Improper ground to the unit.
ACTION 1 Check that the unit is properly ground.
ACTION 2 Install a proper main ground to the unit
1.4
Diagnostic light flashes ignitor
circuit fault.
LED 4 + 7
1.4.1
Open ignitor circuit.
ACTION 1 − Check for correct wiring and loose
connections in the ignitor circuit. Check mult−plug
connections for correct installation.
1.4.2
Broken or failed ignitor.
ACTION 1 − Unplug ignitor and read resistance
across ignitor. If resistance does not read between
25 and 47 ohms, replace the ignitor.
1.5
Diagnostic light flashes low
line voltage
LED 4 + 8
1.5.1
Line voltage is below 90V.
ACTION 1 − Check that the line voltage is above
90V. Determine cause of voltage drop and supply
correct voltage to the control.

Other manuals for Lennox G61MPV

Related product manuals