SPECIFICATIONS - GAS HEAT
Heat Input Type Standard Medium High
Number of Gas Heat Stages 2 2 2
Gas Heating
Performance
Input - Btuh First Stage 84,500 117,000 156,000
Second Stage 130,000 180,000 240,000
Output - Btuh Second Stage 104,000 144,000 192000
Temperature Rise Range - °F 15-45 30-60 40-70
Thermal Efciency 80% 80% 80%
Gas Supply Connections 3/4 in NPT 3/4 in NPT 3/4 in NPT
Recommended Gas Supply
Pressure - in. w.g.
Natural 7 7 7
LPG/Propane 11 11 11
HIGH ALTITUDE DERATE
Units may be installed at altitudes up to 2000 feet above sea level without any modication.
At altitudes above 2000 feet, units must be derated to match gas manifold pressures shown in table below.
NOTE − This is the only permissible derate for these units.
Gas Heat
Type
Altitude
Gas Manifold Pressure
Input Rate
Natural Gas or LPG/Propane
Natural Gas LPG/Propane Gas First Stage Second Stage
ft. In. w.g. In. w.g. Btuh Btuh
Standard 2001-4500 3.4 9.6 84,500 124,000
Medium 2001-4500 3.4 9.6 117,000 172,000
High 2001-4500 3.4 9.6 156,000 230,000