ELECTRICAL DATA 10 TON
10 TON STANDARD EFFICIENCY (R-410A) KGA120S4
1
Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor 1 Rated Load Amps 16 7.8 5.7
Locked Rotor Amps 110 52 38.9
Compressor 2 Rated Load Amps 16 7.8 5.7
Locked Rotor Amps 110 52 38.9
Outdoor Fan
Motors (2)
Full Load Amps 2.4 1.3 1
(total) (4.8) (2.6) (2)
Power Exhaust
(1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 15
Indoor Blower
Motor
Horsepower 3 3 3
Full Load Amps 10.6 4.8 3.9
2
Maximum
Overcurrent
Protection
Unit Only 60 30 20
With (1) 0.33 HP
Power Exhaust
60 30 25
3
Minimum
Circuit
Ampacity
Unit Only 52 25 19
With (1) 0.33 HP
Power Exhaust
54 27 20
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
12.5 TON STANDARD EFFICIENCY (R-410A) KGA150S4
1
Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor 1 Rated Load Amps 19 9.7 7.4
Locked Rotor Amps 123 62 50
Compressor 2 Rated Load Amps 19 9.7 7.4
Locked Rotor Amps 123 62 50
Outdoor Fan
Motors (2)
Full Load Amps 3 1.5 1.2
(total) (6) (3) (2.4)
Power Exhaust
(1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 15
Indoor Blower
Motor
Horsepower 5 5 5
Full Load Amps 16.7 7.6 6.1
2
Maximum
Overcurrent
Protection
Unit Only 70 35 25
With (1) 0.33 HP
Power Exhaust
70 35 25
3
Minimum
Circuit
Ampacity
Unit Only 53 27 22
With (1) 0.33 HP
Power Exhaust
56 29 23
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.