Corp. 1008-L2
LGH SERIES
Service Literature
7.5 to 12.5 ton
38.1 to 70.3 kW
Revised 5/2015
LGH092H through 152U
The LGH092H, 094U, 102H, 120H, 122U, 150S and
152U units are configure to order units (CTO) with a wide
selection of factory-installed options. Units are avail
able in 130,000, 180,000 Btuh or 240,000 Btuh (38.1,
52.7 or 70.3 kW) heating inputs. Gas heat sections are
designed with Lennox' aluminized steel tube heat ex
changers with stainless steel as an option.
Cooling capacities range from 7.5 to 12.5 tons (38.1 to
70.3 kW). All units are equipped with two compressors.
Ultra-high efficiency units are available with an optional di
rect drive blower or belt drive blower equipped with a sup
ply air inverter. Standard and high efficiency units are
available with a belt drive blower equipped with an option
al supply air inverter. The blower will operate at lower
speeds when demand is low and increase to higher
speeds when demand is high.
The following examples show the model numbers of ten-
ton units with all available blower options:
LGH120H4B High Efficiency Belt Drive
LGH120H4M High Efficiency Belt Drive with Inverter
LGH122U4M Ultra High Efficiency Belt Drive with Inverter
LGH122U4E Ultra High Efficiency Direct Drive
Note - Ten-ton units are available in high and ultra high effi
ciencies only.
Standard and high efficiency units come standard with a
lightweight, all-aluminum condenser coil; optional, fin/
tube condenser coils are available. Ultra-high efficiency
units come standard with a tube/fin condenser coil.
Ultra high efficiency units come standard with two single-
speed compressors plumbed in tandem to form a single re
frigerant circuit.
Units are also designed for R410A refrigerant. See unit
nameplate. Operating pressures and pressure switch set
tings are significantly higher than R22 charged units. Ser
vice equipment must be rated for R410A.
Standard and high efficiency units offer mechanical cooling
down to 0°F when properly equipped. Ultra-high efficiency
units offer mechanical cooling down to 40°F.
All LGH units are designed to accept any of several differ
ent energy management thermostat control systems with
minimum field wiring. Factory or field provided control op
tions connect to the unit with jack plugs. When ”plugged in”
the controls become an integral part of the unit wiring.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are
subject to change. Procedures outlined in this manual are
presented as a recommendation only and do not super
sede or replace local or state codes.
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the
proper rigging technique.
3
3
Table of Contents
Options / Accessories Page 2.....................
Specifications Page 8............................
Blower Tables Page 14............................
Electrical Data Page 19...........................
Parts Arrangement Page 25.......................
I-Unit Components Page 28.......................
II-Placement and Installation Page 47...............
III-Charging Page 47..............................
IV-Start Up - Operation Page 55....................
V-System Service Checks Page 57................
High Altitude Page 59.........................
VI-Maintenance Page 59..........................
VII-Accessories Page 60..........................
VIII-Belt Drive Supply Air Inverter Page 67...........
IX-Direct Drive Supply Air Blower Page 70...........
X-Staged Supply Air Operation Page 71.............
XI-Wiring and Operation Sequence Page 72.........
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property va, personal in
jury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer
or equivalent, service agency, or the gas supplier
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
© 2015

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Lennox LGH092H4M and is the answer not in the manual?

Lennox LGH092H4M Specifications

General IconGeneral
BrandLennox
ModelLGH092H4M
CategoryAir Handlers
LanguageEnglish

Summary

Unit Specifications

General Data and Cooling Performance

Key performance metrics including tonnage, capacity, and airflow.

Electrical Data

Unit Components

Gas Heat Components

Details on heat exchangers, burners, ignition controls, and gas valves.

Refrigerant Charging and Procedures

Refrigerant Charge Verification

Procedures for checking and adjusting refrigerant charge levels.

Charging Curves and Tables

Data tables and curves for proper refrigerant charging based on conditions.

Start-Up, Service, and Maintenance

Unit Start-Up Procedures

Steps for initial unit start-up and seasonal checks before operation.

System Service Checks

Diagnostic checks for gas piping, manifold pressure, and flame sensing.

Wiring Diagrams and Sequences

Belt Drive Blower Wiring and Sequence

Wiring diagrams and operational sequences for belt drive blower systems.

Direct Drive Blower Wiring and Sequence

Wiring diagrams and operational sequences for direct drive blower systems.

Troubleshooting

Direct Drive Blower Motor Troubleshooting

Diagnosing and resolving direct drive blower motor faults and errors.