BLOWER DATA
POWER EXHAUST FAN PERFORMANCE
Return Air System Static Pressure Air Volume Exhausted
in. w.g. cfm
0 
0.05 
0.10 
0.15 2410
0.20 
0.25 
 1420
 1200
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT
Electric Heat kW Minimum cfm
7.5 1750
15 2250
22.5 2250
 2750
45 2750
 
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.
Air
Volume
cfm
Wet Indoor Coil
Electric
Heat
Economizer
Filters Return Air
Adaptor
Plate
078, 092 102, 122, 150 MERV 8 MERV 13 MERV 16
1750 0.04 0.04  0.05 0.01   0.00
2000 0.05 0.05   0.01  0.08 0.00
2250   0.04 0.08 0.01 0.04  0.00
2500 0.07 0.07 0.04 0.11 0.01 0.05 0.10 0.00
2750 0.08 0.08 0.05 0.12 0.02 0.05 0.11 0.00
 0.10    0.02  0.12 0.02
 0.11 0.10  0.15 0.02   0.02
 0.12 0.11  0.15  0.07 0.15 0.04
 0.14   0.15  0.08  0.07
4000 0.15 0.14   0.04 0.08 0.17 
4250 0.17 0.15   0.04   0.11
4500  0.17 0.14 0.22 0.04  0.20 0.12
4750 0.20 0.18 0.17 0.25 0.05 0.10 0.21 
5000 0.22 0.20 0.20   0.10  0.18
5250 0.24 0.22 0.22   0.11 0.24 
5500 0.25  0.25  0.07 0.12 0.25 0.22
5750 0.27 0.25  0.45 0.07 0.12 0.27 0.25
  0.27  0.52 0.08  0.28 0.27