Page 24
Blower Data – LRP14AC
Model
No.
Blower Tap
Air Volume (cfm) at Various External Static Pressures - in. w.g.
0.1 0.2 0.30.4 0.50.6 0.
.8
LRP14AC24
Tap 1 (Fan Only) 610 560 525485 430- - -- -
- -
Tap 2 (Low Cooling) 820 795 760720 690650 61
75
Tap 3 (High Cooling) 950 920 880850 820800 76
20
¹ Tap 4 (Low Electric Heat) 820 795 760720 - - -- - -- -
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -820 800760 720
LRP14AC30
Tap 1 (Fan Only) 850 820 780745 710680 63
90
Tap 2 (Low Cooling) 1040 1000 970935 900875 84
15
Tap 3 (High Cooling) 1175 1145 1115 1080 1050 1015 99
45
¹ Tap 4 (Low Electric Heat) 1040 1000 970935 - - -- - -- -
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1050 1015 99
45
LRP14AC36
Tap 1 (Fan Only) 850 800 750700 645600 55
80
Tap 2 (Low Cooling) 1245 1210 1175 1140 1100 1065 1025 975
Tap 3 (High Cooling) 1400 1370 1335 1300 1265 1220 1180 1150
¹ Tap 4 (Low Electric Heat) 1265 1210 1175 1160 - - -- - -- -
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1265 1220 1180 1150
LRP14AC42
Tap 1 (Fan Only) 800 720 640550 475390 31
- -
Tap 2 (Low Cooling) 1470 1410 1360 1300 1260 1210 1155 1095
Tap 3 (High Cooling) 1700 1650 1610 1575 1540 1480 1430 1390
¹ Tap 4 (Low Electric Heat) 1630 1410 1360 1300 - - -- - -- -
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1540 1480 1430 1390
LRP14AC48
Tap 1 (Fan Only) 1145 1075 1000 930850 790740 670
Tap 2 (Low Cooling) 1675 1630 1600 1540 1490 1440 1390 1300
Tap 3 (High Cooling) 1800 1770 1715 1690 1640 1610 1565 1500
¹ Tap 4 (Low Electric Heat) 1675 1630 1600 1560 - - -- - -- -
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1640 1610 1565 1500
LRP14AC60
Tap 1 (Fan Only) 1400 1320 1260 1200 1120 1060 98
00
Tap 2 (Low Cooling) 1920 1870 1820 1770 1720 1670 1450 1360
Tap 3 (High Cooling) 2240 2200 2140 2100 2060 2020 1980 1950
¹ Tap 4 (Low Electric Heat) 1920 1870 1820 1770 - - -- - -- -
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -2060 2020 1980 1950
1